FCU & AHU

Creates A Better Life

23/4/28

Fan coil unit

How to Read the Model Name?

T1 127V 60 Hz Duct Type

F1 Exposed Floor-stand Type (side air intake)

Nominal Air Volume(CFM)

Chilled Water Fan coil unit

C One Way Cassette T DuctA 4 Way Cassette B 4 Way Cassette (Compact)

T2 2nd Generation Duct Type

Type Code

F2 Exposed Flood-stand Type (below air intake)F3 Concealed Flood-stand Type

-- Normal Static Pressure H High Static Pressure

E with Electrical HeaterR Remote Control RA Remote Control with Electrical HeaterFunction Code

T3 New High-static Pressure Type

G Wall-mounted TypeH1 Exposed Ceiling and Floor Type (side air intake)

H2 Exposed Ceiling and Floor Type (back air intake)H3 Concealed Ceiling and Floor Typy

Fan Coil

Ceiling and

Floor

Duct Wall mounted

Floor Standing

Cassette

1-Way4-Way

Compact

4-Way 4 pipes

Cassette

MKCMKBMKA MKD

1.1. Cooling capacity: 5.7~10.4kW;Cooling capacity: 5.7~10.4kW;

2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);

3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);

4.4. Maximum water inlet temp. is 70 ;℃Maximum water inlet temp. is 70 ;℃

Four-way Cassette

Model List:Model List:

*EAH: Electric Auxiliary Heater

Without EAH With EAHMKA-600R MKA-600RA 2100wMKA-750R MKA-750RA 2100wMKA-850R MKA-850RA 2700wMKA-950R MKA-950RA 2700wMKA-1200R MKA-1200RA 2700w

Four-way cassette

Variable color for the panel:

5.5. LED display in the panel;LED display in the panel;6.6. Different color for the panel;Different color for the panel;7.7. Fresh air function;Fresh air function;8.8. Reserve spaces for air side-outletReserve spaces for air side-outlet

3 Pre-cut holeSend air to the nearby room

BlueWhite Grey Black

New design

1.1. Cooling capacity: 3.0~5.5kW;Cooling capacity: 3.0~5.5kW;

2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);

3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);

4.4. Maximum water inlet temp. is 70℃Maximum water inlet temp. is 70℃5.5. Dimension: 580×254×580Dimension: 580×254×580

Four-way Cassette(60*60)

Model List:Model List:Without EAH* With EAH

MKB-300R MKB-300RA 1000wMKB-400R MKB-400RA 1000wMKB-450R / /MKB-500R / /

*EAH: Electric Auxiliary Heater

Compact

1.1. Cooling capacity: 3040w, 3790w;Cooling capacity: 3040w, 3790w;

2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);

3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);

One-way Cassette

Model List:Model List:

Without EAH With EAHMKC-300R MKC-300RA 1000wMKC-400R MKC-400RA 1000w

*EAH: Electric Auxiliary Heater

4-way pipe

Heat water pipe

Chill water pipe

Models MKD-600F

MKD-750F

MKD-850F

MKD-950F

MKD-1200F

MKD-1500F

Cooling capacity(Btu/h) 17406 20239 21058 22867 31672 36109

Heating capacity(Btu/h)

22765 26860 27509 29590 39761 43072

1.1. 2 recycle system,2 pipes per system.2 recycle system,2 pipes per system.

2.2. Save a lot of energies in winter.Save a lot of energies in winter.

3.3. Other function is same as 2 pipe Other function is same as 2 pipe cassette.cassette.

4-way pipe

Heat water pipe

Chill water pipe

Models MKD-300

MKD-400

MKD-500

Cooling capacity(Btu/h) 10236 12624 15354

Heating capacity(Btu/h)

13648 17401 20472

1.1. 2 recycle system,2 pipes per system.2 recycle system,2 pipes per system.

2.2. Save a lot of energies in winter.Save a lot of energies in winter.

3.3. Other function is same as 2 pipe Other function is same as 2 pipe cassette.cassette.

Accessories for cassette

EAH Filter Additional drain pan

3-way valve

Connection kit

Controller

MKA C S O O O SMKB C S O O O SMKC C S O O O SMKD C S O O O SC: the accessories is optional, but it should be assembled in the factory;

S: the accessories is standard;

O: the accessories is optional, it can installed by the installer.

Accessories table:

Block for air outlet hole:

Accessories for cassette

Note: the block is only for four-way cassette(80*80 type).

(Optional)

Accessories for cassette

Additional drain pan (optional):

For 4-way cassette compact For 4-way cassette

Accessories for cassette

3-way valve Connection Kit

Electronic coil

Valve

(Optional) (Optional)

Wireless controller

Wired controller

Central controller

Controllers for cassette

Standard Optional Optional

Note: NIM is necessary if use central controller to control the cassette.

2 Rows

3 Rows

4 Rows

Duct

HSP

MKT2 MKT3 MKT4 MKT5 MKT3H

4 Pipe

Duct (2-Rows without EAH)

1.1. Cooling capacity: 2~13Kw;Cooling capacity: 2~13Kw;2.2. Air return plenums (including filter) are optional (Assembled in factory);Air return plenums (including filter) are optional (Assembled in factory);3.3. For For MKT2H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

12Pa 30(50)PaMKT2-200 MKT2H-200MKT2-300 MKT2H-300MKT2-400 MKT2H-400MKT2-500 MKT2H-500MKT2-600 MKT2H-600MKT2-800 MKT2H-800

MKT2-1000 MKT2H-1000MKT2-1200 MKT2H-1200MKT2-1400 MKT2H-1400

Model List:Model List:

MKT2, MKT2HMKT2, MKT2H

Duct (2-Rows with EAH)

MKT2-xxxE, MKT2H-xxxEMKT2-xxxE, MKT2H-xxxE

Model List:Model List:

12Pa 30(50)Pa EAHMKT2-200E MKT2H-200E 500wMKT2-300E MKT2H-300E 650wMKT2-400E MKT2H-400E 1000wMKT2-500E MKT2H-500E 1000wMKT2-600E MKT2H-600E 1500wMKT2-800E MKT2H-800E 2000w

MKT2-1000E MKT2H-1000E 2000wMKT2-1200E MKT2H-1200E 3000wMKT2-1400E MKT2H-1400E 3000w

1.1. Cooling capacity: 2~13Kw;Cooling capacity: 2~13Kw;2.2. Air return plenums (including filter) are standard;Air return plenums (including filter) are standard;3.3. For For MKT2H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

1.1. Cooling capacity:Cooling capacity: 2.2~12.1kW;2.2~12.1kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. For For MKT3H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Duct (3-Rows without EAH)

12Pa 30(50)PaMKT3-200 MKT3H-200MKT3-300 MKT3H-300MKT3-400 MKT3H-400MKT3-500 MKT3H-500MKT3-600 MKT3H-600MKT3-800 MKT3H-800

MKT3-1000 MKT3H-1000 MKT3-1200 MKT3H-1200

Model List:Model List:

1.1. Air volume: 2.2-17.9 kWAir volume: 2.2-17.9 kW2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Duct (4-Rows without EAH)

30PaMKT4H-200MKT4H-300MKT4H-400MKT4H-500MKT4H-600MKT4H-800

MKT4H-1000MKT4H-1200MKT4H-1500MKT4H-2000

Model List:Model List:

1.1. Air volume: 2.2-17.9 kWAir volume: 2.2-17.9 kW2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Duct (4-Rows with EAH)

30PaMKT4H-200EMKT4H-300EMKT4H-400EMKT4H-500EMKT4H-600EMKT4H-800E

MKT4H-1000EMKT4H-1200EMKT4H-1500EMKT4H-2000E

Model List:Model List:

High Static Pressure Duct (without EAH)

1.1. Cooling capacity: 8.8~19.9kW;Cooling capacity: 8.8~19.9kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

Static PressureMKT3H-800 70Pa

MKT3H-1000 70PaMKT3H-1200 70PaMKT3H-1400 70PaMKT3H-1600 100PaMKT3H-2000 100PaMKT3H-2200 100Pa

Model List:Model List:MKT3H SeriesMKT3H Series

With EAH EAH Static Pressure

MKT3H-800E 3Kw 70PaMKT3H-1000E 3Kw 70PaMKT3H-1200E 3Kw 70PaMKT3H-1400E 3Kw 70PaMKT3H-1600E 10Kw 100PaMKT3H-2000E 10Kw 100PaMKT3H-2200E 10Kw 100Pa

High Static Pressure Duct (with EAH)

Model List:Model List:MKT3H-xxxE SeriesMKT3H-xxxE Series

1.1. Cooling capacity: 8.8~19.9kW;Cooling capacity: 8.8~19.9kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);

4 Pipe ducted type

1 fan 2 fans 4 fans

Models MkT5-200

MkT5-300

MKT5-400

MKT5-500

MKT5-600

MkT5-800

MkT5-1000

MkT5-1200

Cooling capacity(Btu/h) 6826 9215 12287 14676 17065 23208 26621 34812

Heating capacity(Btu/h)

10239 13652 17747 19454 24573 32765 36860 46075

1.For ESP,12Pa and 30Pa are optional.1.For ESP,12Pa and 30Pa are optional.2.The functions are same as 2 pipe ducted type.2.The functions are same as 2 pipe ducted type.

Accessories for duct

EAH Air return plenum &Filter

Additional drain pan

3-way valve

Connection kit

Controller

MKT2No C S O O OYes S S O O O

MKT3 No C S O O O

MKT4No C S O O OYes S S O O O

MKT3HNo C S O O OYes S S O O O

MKT5 No C S O O OC: the accessories are optional, but it should be assembled in the factory;

S: the accessories are standard;

O: the accessories are optional, it can be installed by the installer.

Accessories table:

Air return plenums and electrical heaters:

Accessories for duct

The EAH must be installed in the factory;The air return plenums must be installed in the factory;The duct with EAH must select air return plenums, because the EAH is installed inside the air return plenums;

3-way valve

Electronic coil

Valve

Accessories for duct

(Optional)Connection Kit

(Optional)

Thermostat.

For the units without EAH

For the units with EAH

Controllers for Duct

OptionalOptional

MKF1 MKF2 MKF3 MKF5

Floor Standing

MKF4

ExposedFlat panel

Side intake

ExposedCurving panel

Bottom intake

ExposedFlat panel

Bottom intake

ConcealedExposedCurving panel

Side intake

Floor-standing

Exposed typeExposed type Exposed MKF1-150 MKF2-150MKF1-250 MKF2-250MKF1-300 MKF2-300MKF1-400 MKF2-400MKF1-450 MKF2-450MKF1-500 MKF2-500MKF1-600 MKF2-600MKF1-800 MKF2-800MKF1-900 MKF2-900

Model List:Model List:

MKF1: air return from front side

MKF2: air return from bottom ( standard with foot)

1. Vertical installation on the floor- much more comfortable in heating mode;

2. 3-way valve can be built in the cabinet;

3. Pipe connection can be left or right (installer change it).

Flat type air outlet grill

Exposed type New air outlet grill

Floor-standing

ExposedMKF4-150 MKF5-150MKF4-250 MKF5-250MKF4-300 MKF5-300MKF4-400 MKF5-400MKF4-450 MKF5-450MKF4-500 MKF5-500MKF4-600 MKF5-600MKF4-800 MKF5-800MKF4-900 MKF5-900MKF4: air return from front side

MKF5: air return from bottom ( standard with foot)

Model List:

The grill is modular design- easily removed and cleaned

Floor-standing

Concealed typeConcealed typeModel List:Model List:

ConcealedMKF3-150MKF3-250MKF3-300MKF3-400MKF3-450MKF3-500MKF3-600MKF3-800MKF3-900

1.1. Concealed installation- harmonic with the room Concealed installation- harmonic with the room ;;

Accessories for Floor standing

C: the accessories is optional, but it should be assembled in the factory;

S: the accessories is standard;

O: the accessories is optional, it can installed by the installer.

Accessories table:

Filter Additional drain pan

3-way valve

Connection kit

Controller

Exposed S S O O OConcealed / S O O O

Accessories for Floor standing

3-way valve, connection kit and additional drain pan

3-way valve-Optional

Connection kit-Optional

Thermostat (optional):

Controllers for Floor-standing

KJR-15B/E Simple controller

KJR-15B/E(P) With anti cold air function

The controller can be hided in the cabinet (only for MKF1,2,4,5)

Optional

Optional

MKH2 MKH3

Ceiling and Floor

ExposedCurving panel

Back intake

ConcealedExposedCurving panel

Side intake

MKH1

Ceiling-Floor

Exposed typeExposed type Model List:Model List:

air return from front side

1. Vertical installation on the floor- much more comfortable in heating mode;

2. 3-way valve can be built in the cabinet;

3. Pipe connection can be left or right (installer change it);

4. Ceiling and Vertical installation for optional will be more convenience.

ExposedMKH1-150MKH1-250MKH1-300MKH1-400MKH1-450MKH1-500MKH1-600MKH1-800MKH1-900

Ceiling-Floor

Exposed typeExposed type Model List:Model List:

air return from bottom

1. Vertical installation on the floor- much more comfortable in heating mode;

2. 3-way valve can be built in the cabinet;

3. Pipe connection can be left or right (installer change it);4. Ceiling and Vertical installation for optional will be more convenience.

ExposedMKH2-150MKH2-250MKH2-300MKH2-400MKH2-450MKH2-500MKH2-600MKH2-800MKH2-900

Concealed typeConcealed type Model List:Model List: ConcealedMKH3-150MKH3-250MKH3-300MKH3-400MKH3-450MKH3-500MKH3-600MKH3-800MKH3-900

1.1. Concealed installation- harmonic with the room Concealed installation- harmonic with the room ;;

Ceiling-Floor

Accessories for Ceiling and Floor

C: the accessories is optional, but it should be assembled in the factory;

S: the accessories is standard;

O: the accessories is optional, it can installed by the installer.

Accessories table:

Filter Additional drain pan

3-way valve

Connection kit

Controller

Exposed S S O O OConcealed / S O O O

3-way valve, connection kit and additional drain pan

3-way valve-Optional

Connection kit-Optional

Accessories for Ceiling and Floor

Wall Mounted

MKG-250MKG-300MKG-400MKG-500MKG-600

Model List:Model List:

1.1. Capacity: 2.24~4.5kW;Capacity: 2.24~4.5kW;

2.2. 3-way valve is inside the indoor unit;3-way valve is inside the indoor unit;

3.3. ON/OFF terminal for simple remote control ;ON/OFF terminal for simple remote control ;

4.4. Variable color for the panel;Variable color for the panel;

5.5. Multi direction of pipe connection.Multi direction of pipe connection.

MKG SeriesMKG Series

3-way valve Controller Filter

MKG S S See in next page

S: the accessories are standard;

Accessories for Wall mounted

Accessories table:

Bio filter Silver lon filterGTP filter Deodorization filterAnti- formaldehyde filter Silver lon filterHEAP filter Three-tier healthy filterHEPA air fresh filter Anti-acarus filtervitamin filter Active carbon filterNano photocatalyst filter Bio filterCompound air fresh filter

Accessories for Wall mounted

Filter list:

Wireless Wired controller Central controller

Controllers for wall mounted

Standard Optional Optional

Remark: It doesn’t need NIM when choose CCM.

Air Handle Unit

Dual Skinned Horizontal Type

Dual Skinned Vertical Type

Dual Skinned Ceiling Suspended Type

Standard AHU

Dual Skinned (56 Models)

Horizontal Vertical Ceiling Suspended

Models List

◆ Horizontal Type Air Volume: 2,000 ~ 60,000m3/h Model: MKW2-020W ~ MKW2-600W

◆ Vertical Type Air Volume: 2,000 ~ 60,000m3/h Model: MKW2-020L ~ MKW2-600L

◆ Ceiling Suspended Type Air Volume: 2,000 ~ 15,000m3/h Model: MKS020D1 ~ MKS150D1

Specification

Air Out Type

1 2

Ceiling suspended

V e r t ic a l

1 2

H o r iz o n t a l

3 4