Gas

2
CUADRO RESUMEN DE CALCULO TRAMO CAUDAL LONGITUD LONGITUD EQUI MATERIAL DIAMETRO PRESION Perdida de ESPESORES metros (m) metros (m) Nominal (mm) Interior (mm) Inicial Final Final Calculado (mm) Real (mm) A - B 0.21 1.05 1.26 TUBERÍA ACERO SCH 40 12.70 11.08 0.400 bar 0.16 0.400 bar 0.008 mbar 3.79 0.00 1.62 B - C 0.21 2.68 3.21 TUBERÍA ACERO SCH 40 12.70 11.08 0.400 bar 0.16 0.400 bar 0.021 mbar 3.79 0.00 1.62 C1 - C 0.11 0.50 0.60 TUBERÍA ACERO SCH 40 12.70 11.08 0.400 bar 0.16 0.400 bar 0.001 mbar 1.98 0.00 1.62 C - D 0.32 1.60 1.92 TUBERÍA ACERO SCH 40 12.70 11.08 0.400 bar 0.16 0.400 bar 0.027 mbar 5.77 0.00 1.62 D - E 0.43 0.30 0.36 TUBERÍA ACERO SCH 40 12.70 11.08 0.400 bar 0.16 0.400 bar 0.009 mbar 7.76 0.00 1.62 E - TK 0.43 20.00 24.00 TUBERÍA ACERO SCH 40 12.70 11.08 0.400 bar 0.16 0.398 bar 0.575 mbar 7.82 0.00 1.62 Densidad Relativa 0.52 Coeficiente a Categoria de Emplazamiento 0.40 Coeficiente de Soldadura 1.00 Limite Elastico del Material 2400.00 Presion Maxima de Servicio 17.00 Presion Maxima de Servicio 5.00 PREMISA DE DISEÑO Velocidad (m/s) m 3 (n)/h Carga DP Gas a Media Presion: LA perdida de Carga (Caida de Presion) entre el inicio de la instalacion y el regulador, funcionando la totalidad de los artefactos a instalar, no debe exceder el 5% de la presion de entrada. A C D E1

description

Gas

Transcript of Gas

Hoja1CUADRO RESUMEN DE CALCULOTRAMOCAUDALLONGITUDLONGITUD EQUIMATERIALDIAMETROPRESIONPerdida deVelocidad (m/s)ESPESORESm3 (n)/hmetros (m)metros (m)Nominal (mm)Interior (mm)InicialFinalFinalCarga DPCalculado (mm)Real (mm)A-B0.211.051.26TUBERA ACERO SCH 4012.7011.080.400 bar0.160.400 bar0.008 mbar3.790.001.62B-C0.212.683.21TUBERA ACERO SCH 4012.7011.080.400 bar0.160.400 bar0.021 mbar3.790.001.62C1-C0.110.500.60TUBERA ACERO SCH 4012.7011.080.400 bar0.160.400 bar0.001 mbar1.980.001.62C-D0.321.601.92TUBERA ACERO SCH 4012.7011.080.400 bar0.160.400 bar0.027 mbar5.770.001.62D-E0.430.300.36TUBERA ACERO SCH 4012.7011.080.400 bar0.160.400 bar0.009 mbar7.760.001.62E-TK0.4320.0024.00TUBERA ACERO SCH 4012.7011.080.400 bar0.160.398 bar0.575 mbar7.820.001.62Densidad Relativa0.52Coeficiente a Categoria de Emplazamiento0.40Coeficiente de Soldadura1.00Limite Elastico del Material2400.00Presion Maxima de Servicio 17.00Presion Maxima de Servicio 5.00

PREMISA DE DISEOGas a Media Presion: LA perdida de Carga (Caida de Presion) entre el inicio de la instalacion y el regulador, funcionando la totalidad de los artefactos a instalar, no debe exceder el 5% de la presion de entrada.

ABCDEE1

Hoja2

Hoja3