Guia Service

download Guia Service

of 60

Transcript of Guia Service

  • 7/29/2019 Guia Service

    1/60

    INVERTER

    SERVICE MANUAL

    ROOM AIR CONDITIONERDC INVERTER

    SPLIT WALL-MOUNTED TYPE

    Complete System Name Item Numbers ModelsiDWM26 857620/1 Derby Split Inverter 2.6kWiDWM35 857622/3 Derby Split Inverter 3.5kWiDWM50 857624/5 Derby Split Inverter 5.0kW

    iDWM70 857628/9 Derby Split Inverter 7.0kW

  • 7/29/2019 Guia Service

    2/60

    Table of Contents

    1. Precaution ..................................................................................................................................................... 11.1 Safety Precaution ............................................................................................................................... 11.2 Warning .............................................................................................................................................. 1

    2. Features ......................................................................................................................................................... 33. Dimension ..................................................................................................................................................... 5

    3.1 Indoor Unit ............................................................................................................................................. 53.2 Outdoor Unit .......................................................................................................................................... 6

    4. Specification ................................................................................................................................................. 75. Refrigerant cycle diagram ........................................................................................................................... 86. Wiring diagram ............................................................................................................................................. 9

    6.1 Indoor Unit .......................................................................................................................................... 96.2 Outdoor Unit ..................................................................................................................................... 11

    7. Installation details ...................................................................................................................................... 137.1 Wrench torque sheet for installation ................................................................................................. 137.2 Minimum Electrical Requirements .................................................................................................... 137.3 Pipe Length and the elevation .......................................................................................................... 137.4 Air purging of the piping and indoor unit ........................................................................................... 137.5 Pumping down (Re-installation) ........................................................................................................ 157.6 Re-air purging (Re-installation) ......................................................................................................... 167.7 Balance refrigerant of the 2-way, 3-way valves ................................................................................ 177.8 Evacuation ........................................................................................................................................ 187.9 Gas charging .................................................................................................................................... 19

    8.Capacity Table................. ............................................................................................................................208.1 iDWM26 ............................................................................................................................................ 208.2 iDWM35 ............................................................................................................................................ 218.3 iDWM50 ............................................................................................................................................ 228.4 iDWM70 ............................................................................................................................................ 23

    9. Electronic function ..................................................................................................................................... 24

  • 7/29/2019 Guia Service

    3/60

    9.1 Abbreviation ...................................................................................................................................... 249.2 Display function ................................................................................................................................ 249.3 Protection .......................................................................................................................................... 259.4 Fan-Only Mode ................................................................................................................................. 269.5 Cooling Mode .................................................................................................................................... 269.6 Drying mode ..................................................................................................................................... 289.7 Heating mode ................................................................................................................................... 299.8 Auto Mode Function ......................................................................................................................... 319.9 Forced operation function ................................................................................................................. 329.10 Action of 4-way valve ........................................................................................................................ 329.11 Two speeds outdoor fan function ..................................................................................................... 329.12 Timer function ................................................................................................................................... 329.13 Sleep function mode ......................................................................................................................... 339.14 Auto-Restart function ........................................................................................................................ 33

    10. Troubleshooting ....................................................................................................................................... 3410.1 Indoor Unit Error Display .................................................................................................................. 3510.2 Diagnosis and Solution ..................................................................................................................... 3610.3 Key Part Checking ............................................................................................................................ 39

    11. Explosion Diagrams ................................................................................................................................. 4111.1 IDWMG26 - INDOOR ....................................................................................................................... 4111.2 IDWMZ26 - OUTDOOR .................................................................................................................... 4311.3 IDWMG35 - INDOOR ....................................................................................................................... 4511.4 IDWMZ35 - OUTDOOR .................................................................................................................... 4711.5 IDWMG50 - INDOOR .......................................................................................................................4911.6 IDWMZ50 - OUTDOOR .................................................................................................................... 5111.7 IDWMG70 - INDOOR ........................................................................................................................5311.8 IDWMZ70 - OUTDOOR .................................................................................................................... 55

  • 7/29/2019 Guia Service

    4/60

    1

    1. Precaution1.1 Safety Precaution

    To prevent injury to the user or other

    people and property damage, the following

    instructions must be followed.

    Incorrect operation due to ignoring

    instruction will cause harm or damage.

    Before service unit, be sure to read

    this service manual at first.

    1.2 Warning

    Installation

    Do not use a defective or underrated circuit

    breaker. Use this appliance on a dedicated

    circuit.There is risk of fire or electric shock.

    For electrical work, contact the dealer,

    seller, a qualified electrician, or an Authorized

    service center.Do not disassemble or repair the product, there

    is risk of fire or electric shock.Always ground the product.

    There is risk of fire or electric shock.

    Install the panel and the cover of control

    box securely.

    There is risk of fire or electric shock.Always install a dedicated circuit

    and breaker.Improper wiring or installation may cause fire or

    electric shock.Use the correctly rated breaker of fuse.

    There is risk of fire or electric shock.

    Do not modify or extend the power cable.

    There is risk of fire or electric shock.

    Do not install, remove, or reinstall the unit

    by yourself (customer).There is risk of fire, electric shock, explosion,

    or injury.Be caution when unpacking and

    installing the product.Sharp edges could cause injury, be

    especially careful of the case edges and the

    fins on the condenser and evaporator.For installation, always contact the dealer

    or an Authorized service center.There is risk of fire, electric shock, explosion,

    or injury.Do not install the product on a defective

    installation stand.It may cause injury, accident, or damage to

    the product.Be sure the installation area does

    not deteriorate with age.If the base collapses, the air conditioner could fall

    with it, causing property damage, product failure,and personal injury.

    Do not let the air conditioner run for a

    long time when the humidity is very high and a

    door or a window is left open.Moisture may condense and wet or

    damage furniture.Take care to ensure that power cable could

    not be pulled out or damaged during operation.There is risk of fire or electric shock.

    Do not place anything on the power cable.

    There is risk of fire or electric shock.

    Do not plug or unplug the power supply

    plug during operation.There is risk of fire or electric shock.

    Do not touch (operation) the product with

    wet hands.There is risk of fire or electric shock.

    Do not place a heater or other appliance

    near the power cable.There is risk of fire and electric shock.

    Do not allow water to run into electric parts.It may cause fire, failure of the product, or electricshock.

    Do not store or use flammable gas

    or combustible near the product.There is risk of fire or failure of product.

    Do not use the product in a tightly

    closed space for a long time.Oxygen deficiency could occur.

    When flammable gas leaks, turn off the gas

    and open a window for ventilation before turning

    the product on.Do not use the telephone or turn switches on or

    off. There is risk of explosion or fire.If strange sounds or smoke comes from

    product, turn the breaker off or disconnect the

    power supply cable.There is risk of electric shock or fire.

    Stop operation and close the window in

    storm or hurricane. If possible, remove the

    product from the window before the hurricane

    arrives.

  • 7/29/2019 Guia Service

    5/60

    2

    There is risk of property damage, failure of

    product, or electric shock.Do not open the inlet grill of the product

    during operation. (Do not touch the

    electrostatic filter, if the unit is so equipped.)There is risk of physical injury, electric shock,

    or product failure.When the product is soaked (flooded

    or submerged), contact an Authorized

    service center.There is risk of fire or electric shock.

    Be caution that water does not enter the

    product.There is risk of fire, electric shock, or

    product damage.Ventilate the product from time to time

    when operating it together with a stove, etc. There is risk of fire or electric shock.

    Turn the main power off when cleaning

    or maintaining the product.There is risk of electric shock.

    When the product is not be used for a

    long time, disconnect the power supply plug or

    turn off the breaker.There is risk of product damage or failure,

    or unintended operation.Take care to ensure that nobody could

    step on or fall onto the outdoor unit.This could result in personal injury and

    product damage.

    CAUTION

    Always check for gas (refrigerant) leakageafter installation or repair of product.Low refrigerant levels may cause failure of product.

    Install the drain hose to ensure that water

    is drained away properly.A bad connection may cause water leakage.

    Keep level even when installing the product.

    To avoid vibration of water leakage.

    Do not install the product where the noise

    or hot air from the outdoor unit could

    damage the neighbourhoods.It may cause a problem for your neighbours.

    Use two or more people to lift and

    transport the product.Avoid personal injury.

    Do not install the product where it will

    be exposed to sea wind (salt spray) directly.

    It may cause corrosion on the product.

    Corrosion, particularly on the condenser and

    evaporator fins, could cause product malfunction

    or inefficient operation.

    Operational

    Do not expose the skin directly to cool airfor long periods of time. (Do not sit in the draft).This could be harmful to your health.

    Do not use the product for special

    purposes, such as preserving foods, works of

    art, etc. It is a consumer air conditioner, not a

    precision refrigerant system.There is risk of damage or loss of property.

    Do not block the inlet or outlet of air flow.

    It may cause product failure.

    Use a soft cloth to clean. Do not use harsh

    detergents, solvents, etc.There is risk of fire, electric shock, or damage to the

    plastic parts of the product.Do not touch the metal parts of the product

    when removing the air filter. They are very sharp.There is risk of personal injury.

    Do not step on or put anything on the

    product. (outdoor units)There is risk of personal injury and failure of product.

    Always insert the filter securely. Clean the

    filter every two weeks or more often if necessary.A dirty filter reduces the efficiency of the air

    conditioner and could cause product malfunction or

    damage.Do not insert hands or other object through

    air inlet or outlet while the product is operated.There are sharp and moving parts that could

    cause personal injury.Do not drink the water drained from the

    product.It is not sanitary. Could cause serious health issues.

    Use a firm stool or ladder when cleaning or

    maintaining the product.Be careful and avoid personal injury.

    Replace all the batteries in the remotecontrol with new ones of the same type. Do not

    mix old and new batteries or different types of

    batteries.There is risk of fire or explosion.

    Do not recharge or disassemble the

    batteries. Do not dispose of batteries in a fire.They may burn of explode.

    If the liquid from the batteries gets ontoyour skin or clothes, wash it well with cleanwater. Do not use the remote of the batteries that

    has leaked.The chemical in batteries could cause burns or otherhealth hazards.

  • 7/29/2019 Guia Service

    6/60

    2. Features

    Indoor unitOperation by remote controllerSensing by room temperature

    Room temperature sensor (T1)Indoor Coil temperature sensor (T2)

    Room temperature controlMaintain the room temperature in accordance with the

    setting temperature.Anti-freezing control in cooling

    Prevent the water being frozen on evaporator by sensing

    the evaporator pipe temperature in cooling modeTime Delay Safety control

    Restarting is for approx. 3 minutesIndoor fan speed control

    Turbo wind, high, med, low, breezeTwo-direction air vane

    The unit will decide the louver direction according to

    operation mode.Sleep mode auto control

    The fan is turned to low speed (cooling/heating)The unit will turn off at the seventh hour.

    Independent dehumidificationThe function is usually used in rainy days in

    springtime or damp areas.

    Air flow Direction controlThe louver can be set at the desired position or

    swing up and down automaticallyAuto mode

    The mode can be change by the room temperature.Temp. Compensation

    Work voltage (160V-253V)

    Self-diag. function

    Anti-cold functionPrevent the cold wind at

    the beginning of unit start.Auto defrost

    Auto-restart functionWhen the power supply is interrupted

    and then restored, the air conditioner

    automatically restores the previous

    function setting.Flexible wiring connection

    3

  • 7/29/2019 Guia Service

    7/60

    Outdoor unit

    Power delay controlThe unit has 3 mins delay between continuously ON/OFF operations.

    Low noise air flow systemBird tail propeller fan makes the outdoor unit run more quietly.

    Hydrophilic aluminium finThe hydrophilic fin can improve the heating efficiency at operation mode.

    4 way valve controlIt is only operated in the heating operation mode except defrosting operation.

    Anti-rust cabinetMade from electrolytic zinc steel sheet and anti-rust coated components

    Valve protection coverIt protects the valves and prevents water from dripping.

    Discharge pipe temperature protect

    Driving heating at -15C

    4

  • 7/29/2019 Guia Service

    8/60

    C

    3. Dimension

    3.1 Indoor Unit

    B A

    Model Name A (mm) B (mm) C (mm)iDWMG26 790 195 265

    iDWMG35 790 195 265

    iDWMG50 920 225 295

    iDWMG70

    1250mm230mm

    325mm

    5

  • 7/29/2019 Guia Service

    9/60

    3.2 Outdoor Unit

    MODEL NAME A(mm) B(mm) C(mm) D(mm) E(mm)

    iDWMZ26 590 530 760 290 315

    iDWMZ35 590 530 760 290 315iDWMZ50 695 560 845 335 360

    iDWMZ70 860 590 895 330 355

    Gas side Flare9.53 iDWM2612.7 iDWM3512.7 iDWM5016.0 iDWM70

    Liquid side Flare6.35 iDWM266.35 iDWM356.35 iDWM509.53 iDWM70

    A

    DE

    Service Port

    B

    C

    6

  • 7/29/2019 Guia Service

    10/60

    iDWM26 iDWM35 iDWM50 iDWM70

    iDWMG26 iDWMG35 iDWMG50 iDWMG70

    iDWMZ26 iDWMZ35 iDWMZ50 iDWMZ70

    Ph-V-Hz 1,220-240V~,50Hz 1, 220-240V~, 50Hz 1,220-240V~,50Hz 1,220-240V~,50Hz

    Rated Capacity(Min~Max) kW 2.55(0.90~3.25) 3.40(1.10~4.30) 4.95(1.55~6.74) 7.00(3.50-7.30)

    Rated Input (Min~Max) kW 0.68(0.30~1.10) 0.99(0.40~1.48) 1.60(0.40~2.30) 2.25(0.84-2.35)

    Rated current A 3.0 4.4 7.2 10.0

    Rated EER 3.75 3.43 3.09 3.1

    Rated Capacity (Min~Max) kW 2.93(0.96~3.60) 3.81(1.17~4.45) 4.85(1.50~6.45) 7.20(3.20-7.50)

    Rated Input (Min~Max) kW 0.68(0.31~1.15) 0.99(0.39~1.46) 1.55(0.36~2.10) 2.18(0.72-2.72)

    Rated current A 3.0 4.4 6.5 9.4

    Rated COP 4.30 3.85 3.13 3.3

    l/h 0.8 1.2 1.5 2.6

    A 8.00 8.50 15.00 15.00

    A 3.20 4.50 10.20 15.00

    Model DA108X1C-20FZ3 DA108X1C-20FZ3 C-6RVN93H0N C-6RZ146H1A

    Type Rotary Rotary Rotary Rotary

    Brand TOSHIBA TOSHIBA SANYO SANYO

    Capacity kW 3.2 3.2 4.2 6.4

    Input kW 0.855 0.855 1.010 1.630

    Rated current(RLA) A 5.30 5.30 6.23 8.38

    Locked rotor Amp(LRA) A 8 8 13.26 12.50

    Thermal protector CS-74 CS-74 1NT11L-3979 1NT11L-3979

    Capacitor uF No No No No

    Refrigerant oil ml 480 480 400 FV50BX / 350

    Model RPG20D RPG20D RPG28D YDK50-4E

    Brand Welling Welling Welling Welling

    Input W 43 43 47 67

    Capacitor uF 1.5 1.5 1.5 3.0

    Speed(hi/mi/lo) r/min 1250/1050/900 1250/1050/900 1180/1100/950 1250/1120/1030

    a.Number of rows 2 2 2 2

    b.Tube pitch(a)x row pitch(b) mm 21x13.37 2113.37 21x13.37 21x13.37

    c.Fin spacing mm 1.3 1.3 1.3 1.3

    d.Fin type (code) Hydrophi lic aluminium Hydrophil ic aluminium Hydrophilic aluminium Hydrophilic aluminium

    e.Tube outside dia.and type mm 7, innergroove tube 7, innergroove tube 7, innergroove tube 7, innergroove tube

    f.Coil length x height x width mm 637*294*26.74 637x294x26.74 755x210x26.74+725x126x26.74 965x420x26.74

    g.Number of circuits 2 2 4 6

    l/s 164/130/90 171/135/90 222/194/167 322/286/250

    dB(A) 40/37/33 43/40/36 44/40/37 51/48/45

    Dimension (W*D*H) mm 790x195x265 790x195x265 920x225x292 1250230x325

    Packing (W*D*H) mm 875x285x375 875x285x375 1015x295x368 1345335x430

    Net/Gross weight Kg 9/11 9/11 11.5/15 17/21

    Model YDK24-6G YDK24-6G YDK53-6F YDK53-6N

    Brand Welling Welling Welling Welling

    Input W 59 59 126/106 144/102

    Capacitor uF 2.5 2.5 2.5 2.5

    Speed r/min 800/550 800/550 760/600 780/630

    a.Number of rows 2 2 2 2

    b.Tube pitch(a)x row pitch(b) mm 22x19.05 22x19.05 25.4x22 21x13.37

    c.Fin spacing mm 1.4 1.4 1.6 1.3

    d.Fin type (code) Hydrophi lic aluminium Hydrophil ic aluminium Hydrophilic aluminium Hydrophilic aluminium

    e.Tube outside dia.and type mm 7.94, innergroove tube 7.94, innergroove tube 9.52, innergroove tube 7.94 innergroove tube

    f.Coil length x height x width mm 656x550x38.1 656x550x38.1 766x660x44 965x420x26.74

    g.Number of circuits 4 4 4 6

    l/s 458/294 458/294 694/555 833/694

    dB(A) 52/50 53/51 56/54 60/54

    Dimension(W*D*H) mm 760x285x590 760x285x590 845x335x695 895330x860

    Packing (W*D*H) mm 887x355x645 887x355x645 965x395x755 1043395915

    Net/Gross weight Kg 40.5/43 40.5/43 52/56 63.5/67.5

    g 1100 1100 1700 2200

    MPa 4.2/1.5 4.2/1.5 4.2/1.5 4.2/1.5

    Liquid side/ Gas side mm(inch) 6.35/9.53 (1/4"/3/8") 6.35/12.7 (1/4"/1/2") 6.35/12.7 (1/4"/1/2") 9.53/16.0(3/8"/5/8")

    Max. refrigerant pipe length m 15 15 15 25

    Max. difference in level m 8 8 8 10

    10A 10A 20A No plug

    Electronic control Electronic control Electronic control Electronic control

    17 ~ 30 17 ~ 30 17 ~ 30 17 ~ 30

    -15 ~ 50 -15 ~ 50 -15 ~ 50 -15 ~ 50

    m2 16-24 20-30 28 ~ 40 35~58

    set 89/196/232 89/196/232 70/146/168 47/98/112

    dB(A) 6163

    66 71m 5 5 5 5Pre-Charged Length

    Design pressure (Hi/Lo)

    Refrigerant piping

    Compressor

    Starting current

    Outdoor sound power level

    Qtyper 20 /40 /40'HQ

    Thermostat type

    Operation temp

    Ambient temp (Outdoor)

    Indoor fan motor

    Recommended application area

    Outdoor coil

    Outdoor unit

    Plug type

    Indoor air flow (Hi/Mi/Lo)

    Indoor

    Outdoor air flow (Hi/Lo)

    Outdoor

    Outdoor noise level (SPL @ 1 meter)

    Refrigerant type R410A (Pre-charge)

    Model

    Moisture Removal

    Indoor unit

    Outdoor fan motor

    Cooling

    Heating

    Power supply

    Indoor coil

    Indoor noise level (Hi/Mi/Lo) @ 1 meter (SPL)

    Max. current

    7

    The above design and specications are subject to change without prior notice for product development.

  • 7/29/2019 Guia Service

    11/60

    5. Refrigerant cycle diagram

    8

  • 7/29/2019 Guia Service

    12/60

    6. Wiring diagram6.1 Indoor Unit

    iDWMG26, iDWMG35

    iDWMG50

    9

  • 7/29/2019 Guia Service

    13/60

    iDWMG70

    10

  • 7/29/2019 Guia Service

    14/60

    6.2 Outdoor UnitiDWMZ26, iDWMZ35

    iDWMZ50

    11

  • 7/29/2019 Guia Service

    15/60

    iDWMZ70

    12

  • 7/29/2019 Guia Service

    16/60

    7. Installation details

    7.1 Wrench torque sheet for installation

    Outside diameter Torquemm inch Kgf.m

    6.35 1/4 1.8

    9.52 3/8 4.2 12.7 1/2 5.5

    16.0 5/8 6.6

    7.2 Minimum Electrical Requirements

    Conductor sizes are based on using TYPE D Circuit Breaker Protection and maximum cable length shall not exceed 15m.Incoming Power supply

    Model Maximum run current

    (A)

    Rated run current

    (A)Circuit Breaker size (A) Minimum Conductor size

    mm2

    iDWM26 8 3 10 1.0

    iDWM35 8.5 4.4 10 1.0

    iDWM50 15 7.2 20 2.5

    iDWM70 15 10 25 2.5Interconnecting Cables Requirements

    Models Inter-connecting supply to Minimum conductor size mm Remarks

    iDWM26 Compressor+Neutral+Earth 2x1.0 mm+ Earth Power supply to indoor

    first4 way valve + Outdoor fan 2x1.0 mm

    iDWM35 Compressor+Neutral+Earth 2x1.0 mm+ Earth Power supply to indoor

    first4 way valve + Outdoor fan 2x1.0 mm

    iDWM50 Compressor+Neutral+Earth 2x2.5 mm+ Earth Power supply to indoor

    first4 way valve + Outdoor fan 2x1.0 mm

    iDWM70 Indoor Unit 2x1.0 mm2

    + Earth Power supply to outdoorfirst4 way valve + Outdoor fan 2x1.0 mm

    NOTE: The supply voltage should be consistent with the rated voltage of the air conditioner

    7.3 Pipe Length and the elevationModel Pipe size (mm) Pre-charged

    length (m)Max.

    ElevationB(m)

    Max. LengthA(m)

    AdditionalRefrigerant (g/m)Gas Liquid

    iDMW26 9.53 (3/8) 6.35 (1/4) 5 8 15 20iDWM35 12.7 (1/2) 6.35 (1/4) 5 8 15 20

    iDWM50 12.7 (1/2) 6.35 (1/4) 5 8 15 20iDWM70 16.0 (5/8) 9.53 (3/8) 5 10 25 40

    Caution:

    Capacity is based on standard length and maximum allowance length is base of reliability.

    Oil trap should be installed per 5-7 meters.

    7.4 Air purging of the piping and indoor unit

    Required tools:

    Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.

    13

    Signal Wire

    Signal Wire

    Signal Wire

    Signal Wire 1

    1

    1

    1

  • 7/29/2019 Guia Service

    17/60

    Note: The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect

    thecompressor, reduces the cooling capacity, and could lead to a malfunction of unit.Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the

    gas leakage from the refrigeration cycle.

    Procedure1) Recheck the piping connections.

    2) Open the valve stem of the 2-way valve

    counter clockwise approximately 90, wait 10

    seconds, and then set it to closed position.

    Be sure to use a hexagonal wrench to operate

    the valve stem.

    3) Check for gas leakage.

    Check the flare connection for gas leakage

    4) Purge the air from the system.

    Set the 2-way valve to the open position and

    remove the cap from the 3-way valves

    service port.

    Using the hexagonal wrench to press the valve

    core pin, discharge for three seconds and then

    wait for one minute.

    5) Use torque wrench to tighten the service port

    cap to a torque of 1.8 kgf.m. (18N.m)

    6) Set the 3-way valve to the opened position.

    7) Mounted the valve stem nuts to the 2-way and

    3-way valves.8) Check for gas leakage.

    At this time, especially check for gas leakage from

    the 2-way and 3-way stem nuts, and from the

    service port.Caution:

    If gas leakage is discovered in step (3) above, take the

    following measures.If the leaks stop when the piping connections are

    tightened further, continue working from step (4).If the gas leaks do not stop when the connections are

    retightened, repair the location of the leak, discharge all of

    the gas through the service port, and then recharge with

    the specified amount of gas from a gas cylinder.

    14

  • 7/29/2019 Guia Service

    18/60

    7.5 Pumping down (Re-installation)

    Procedure1) Confirm that both the 2-way and 3-way valves are set to the opened position.

    Remove the valve stem caps and confirm that the valve stems are in the opened

    position. Be sure to use a hexagonal wrench to operate the valve stems.

    2) Operate the unit for 10 to 15 minutes.

    3) Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way valve.

    Connect the charge hose with the push pin to the gas service port.4) Air purging of the charge hose.

    Open the low-pressure valve on the charge set slightly to purge air from the charge hose.

    5) Set the 2-way valve to the close position.

    6) Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.

    7) Immediately set the 3-way valve to the closed position.

    Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.

    Disconnect the charge set, and amount the 2-way and 3-way valves stem nuts and service port caps. Use a

    torque wrench to tighten the service port cap to a torque of 1.8 kgf.m. Be sure to check for gas leakage.

    Close

    15

  • 7/29/2019 Guia Service

    19/60

    7.6 Re-air purging (Re-installation)

    Procedure:1) Confirm that both the 2-way and 3-way valves are set to the closed position.

    2) Connect the charge set and a charging cylinder to the service port of the 3-way

    valve. Leave the valve on the charging cylinder closed.

    3) Air purging.

    Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-

    way valve approximately 45 for 3 seconds then closing it for 1 minute; repeat 3 times.

    After purging the air, use a torque wrench to tighten the flare nut to on the 2-way valve.

    4) Check the gas leakage.

    Check the flare connections for gas leakage.

    5) Discharge the refrigerant.

    Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicates 0.3 to 0.5 MPa.

    6) Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open

    position. Be sure to use a hexagonal wrench to operate the valve stems.

    7) Mount the valve stems nuts and the service port cap.

    Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m. Be sure to check the gas

    leakage.

    16

  • 7/29/2019 Guia Service

    20/60

    7.7 Balance refrigerant of the 2-way, 3-way valves

    Procedure:1) Confirm that both the 2-way and 3-way valves are set to the open position.

    2) Connect the charge set to the 3-way valves service

    port. Leave the valve on the charge set closed.

    Connect the charge hose with the push pin to the service port.

    3) Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.05

    to 0.1MPa.

    If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than

    0.1MPa], discharge the refrigerant until the gauge indicates 0.05 to 0.1 MPa. If this is the case, it will not be

    necessary to apply an evacuation.

    Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil will be discharged.

    17

  • 7/29/2019 Guia Service

    21/60

    7.8 Evacuation

    Procedure:1) Connect the vacuum pump to the charge sets centre hose.

    2) Evacuation for approximately one hour.

    Confirm that the gauge needle has moved toward -0.1 MPa (-76 cmHg) [vacuum of 4 mmHg or less].

    3) Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge

    needle does not move (approximately 5 minutes after turning off the vacuum pump).

    4) Disconnect the charge hose from the vacuum pump.

    Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needed.

    18

  • 7/29/2019 Guia Service

    22/60

    7.9 Gas charging

    Procedure:1) Connect the charge hose to the charging cylinder.

    Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.

    2) Purge the air from the charge hose.

    Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air

    (be careful of the liquid refrigerant).

    3) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.

    If the system cannot be charged with the specified amount of refrigerant, it can be charged with a little at a time

    (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not

    sufficient, wait approximately 1 minute and then repeat the procedure.(pumping down-pin).

    4) Immediately disconnect the charge hose from the 3-way valves service port. Stopping partway will allow the

    refrigerant to be discharged.

    If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air

    conditioner before disconnecting the hose.

    5) Mount the valve stem caps and the service port

    Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.

    19

  • 7/29/2019 Guia Service

    23/60

    8. Capacity Table8.1 iDWM26

    SUMMER OUTDOOR TEMPERATURE DRY

    Indoor

    Conditions25C 30C 35C 40C 45C 50C

    21C D15C W

    Total capacity W 2393 2275 2117 1944 1785 1665

    Sensitive capacity W 1753 1700 1626 1543 1464 1401

    Input W. 564 612 660 708 757 805

    24C D17C W

    Total capacity W 2565 2451 2312 2165 2023 1901

    Sensitive capacity W 1860 1805 1740 1677 1628 1606

    Input W. 564 617 669 721 774 826

    27C D19C W

    Total capacity W 2745 2694 2549 2351 2140 1955

    Sensitive capacity W 2016 1973 1898 1807 1714 1636

    Input W. 575 629 683 736 790 844

    32C D23C W

    Total capacity W 2797 2841 2801 2704 2578 2451

    Sensitive capacity W 1910 1933 1917 1885 1862 1871

    Input W. 570 633 696 759 821 884

    WINTER OUTDOOR CONDITIONS

    Indoor

    Conditions

    12C D11C W

    7C D6C W

    4C D3C W

    0C D-1C W

    -4C D-6C W

    -7C D-8C W

    15C

    Capacity W 3435 3057 2703 1747 1461 1408

    Input W. 740 660 592 510 474 500

    18C

    Capacity W 3235 2901 2615 1661 1533 1355

    Input W. 757 660 602 543 524 549

    20C

    Capacity W 3218 2930 2592 1578 1418 1385

    Input W. 778 684 617 543 514 541

    22C

    Capacity W 2992 2850 2473 1339 1433 1337

    Input W. 719 679 618 541 518 567

    20

  • 7/29/2019 Guia Service

    24/60

    8.2 iDWM35

    SUMMER OUTDOOR TEMPERATURE DRY

    Indoor

    Conditions25C 30C 35C 40C 45C 50C

    21C D15C W

    Total capacity W 3300 3137 2919 2681 2461 2296

    Sensitive capacity W 2337 2266 2167 2057 1951 1867

    Input W. 804 873 942 1010 1079 1148

    24C D17C W

    Total capacity W 3537 3379 3188 2985 2789 2622

    Sensitive capacity W 2478 2406 2319 2235 2170 2140

    Input W. 805 879 954 1029 1103 1178

    27C D19C W

    Total capacity W 3785 3715 3515 3242 2950 2696

    Sensitive capacity W 2686 2629 2529 2408 2284 2180

    Input W. 821 897 974 1050 1127 1204

    32C D23C W

    Total capacity W 3856 3918 3863 3729 3555 3379

    Sensitive capacity W 2545 2576 2555 2512 2481 2493

    Input W. 813 902 992 1082 1172 1262

    WINTER OUTDOOR CONDITIONS

    Indoor

    Conditions

    12C D11C W

    7C D6C W

    4C D3C W

    0C D -1C W

    -4C D -6C W

    -7C D -8C W

    15C

    Capacity W 4467 3975 3515 2272 1899 1830

    Input W. 1077 962 862 743 690 728

    18C

    Capacity W 4207 3772 3401 2160 1994 1761

    Input W. 1103 961 877 791 763 800

    20C Capacity W 4184 3810 3371 2051 1845 1801

    Input W. 1132 996 899 791 748 787

    22C

    Capacity W 3890 3706 3216 1742 1863 1739

    Input W. 1047 989 900 788 754 825

    21

  • 7/29/2019 Guia Service

    25/60

    8.3 iDWM50

    WINTER OUTDOOR CONDITIONS

    Indoor

    Conditions

    12C D11C W

    7C D6C W

    4C D3C W

    0C D-1C W

    -4C D-6C W

    -7C D-8C W

    15CCapacity W 5686 5060 4474 2892 2418 2330

    Input W. 1686 1505 1349 1163 1081 1140

    18C

    Capacity W 5355 4802 4329 2749 2538 2242

    Input W. 1726 1505 1373 1238 1195 1252

    20CCapacity W 5326 4850 4291 2611 2348 2292

    Input W. 1773 1559 1407 1238 1172 1232

    22CCapacity W 4952 4717 4094 2217 2371 2214

    Input W. 1640 1548 1410 1234 1180 1292

    SUMMER OUTDOOR TEMPERATURE DRY

    Indoor

    Conditions25C 30C 35C 40C 45C 50C

    21C D15C W

    Total capacity W 4645 4417 4109 3774 3465 3232

    Sensitive capacity W 3507 3401 3252 3086 2928 2802

    Input W. 1326 1440 1553 1667 1780 1894

    24C D17C W

    Total capacity W 4979 4757 4488 4202 3927 3691

    Sensitive capacity W 3720 3611 3480 3354 3256 3212

    Input W. 1328 1451 1574 1697 1820 1943

    27C D19C W

    Total capacity W 5329 5230 4948 4564 4153 3795

    Sensitive capacity W 4031 3945 3796 3614 3429 3272

    Input W. 1354 1480 1606 1733 1859 1985

    32C D23C W

    Total capacity W 5429 5516 5438 5250 5005 4757

    Sensitive capacity W 3820 3867 3834 3770 3723 3742

    Input W. 1340 1488 1637 1785 1933 2081

    22

  • 7/29/2019 Guia Service

    26/60

    8.4 iDWM70

    Summer Outdoor Temperature Day

    Indoor

    Conditions 25C 30C 35C 40C 45C 50C

    21C D15C W

    Total capacity W 6710 6380 5935 5452 5005 4669

    Sensitive capacity W 4937 4788 4579 4345 4122 3945

    Input W. 1915 2078 2242 2406 2570 2734

    24C D17C W

    Total capacity W 7193 6871 6483 6070 5672 5331

    Sensitive capacity W 5237 5083 4900 4722 4584 4522

    Input W. 1917 2094 2272 2450 2628 2805

    27C D19C W

    Total capacity W 7697 7554 7148 6592 5999 5482

    Sensitive capacity W 5676 5555 5344 5087 4827 4606

    Input W. 1954 2137 2319 2501 2684 2866

    32C D23C W

    Total capacity W 7841 7967 7855 7583 7229 6871

    Sensitive capacity W 5378 5444 5398 5308 5242 5268

    Input W. 1935 2149 2363 2577 2791 3005

    WINTER OUTDOOR CONDITIONS

    IndoorConditions

    12C D11C W

    7C D6C W

    4C D3C W

    0C D-1C W

    -4C D-6C W

    -7C D-8C W

    15C

    Capacity W 8864 7887 6974 4509 3769 3632

    Input W. 2492 2224 1994 1718 1596 1684

    18C

    Capacity W 8347 7485 6748 4285 3956 3495

    Input W. 2550 2224 2028 1829 1766 1850

    20C

    Capacity W 8303 7560 6689 4070 3660 3573

    Input kW. 2619 2304 2079 1829 1731 1821

    22C

    Capacity W 7719 7353 6382 3456 3696 3451

    Input kW. 2422 2287 2082 1823 1743 1908

    23

  • 7/29/2019 Guia Service

    27/60

    9. Electronic function9.1 Abbreviation

    T1: Room temperature sensorT2: Indoor Coil temperature sensorT3: Outdoor coil temperature sensorT4: Outdoor ambient temperature sensor

    Te: CompressorDischarge temperature sensor

    9.2 Display function9.2.1 Icon explanation on indoor display board for models iDWMG26, iDWMG35, iDWMG50.

    iDWMG26, iDWMG35, iDWMG50

    1) AUTO indicator

    This indicator illuminates when the air conditioner is in AUTO operation.

    2) TIMER indicator

    This indicator illuminates when TIMER is set ON/OFF.

    3) DEF. Indicator

    This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air

    control feature is activated in heating mode.4) TEMPERATURE indicator

    Displays the temperature settings. When changing the setting temperature, this indicator begins to flash and

    stops 20 seconds later.

    Displays the room temperature when the air conditioner is in FAN only operation, and the range of that is

    0~50C.

    No display when the unit stops.

    Displays the malfunction code or protection code if the unit malfunctions.5) FREQUENCY indicator

    This indicator appears only when the compressor is in operation and indicates the current operating

    frequency. This indicator will flash when the power is on and the unit is not in operation.

    24

  • 7/29/2019 Guia Service

    28/60

    9.2.2 Icon explanation on indoor display board for model iDWMG70

    iDWMG70

    1) POWER Indicator:

    The indicator flashes once every second after power is on and illuminates when the air conditioner is in operation.

    2) TIMER indicator:

    The indicator illuminates when TIMER is set ON/OFF.

    3) DEFROST indicator:

    This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air control feature is

    activated in heating operation.

    4) AUTO indicator:

    This indicator illuminates when the air conditioner is in AUTO operation.

    5) DIGITAL DISPLAY:

    Displays the temperature settings. When changing the setting temperature, this indicator begins to flash, and stops

    20 seconds later.

    Displays the room temperature when the air conditioner is in FAN only operation.

    Displays the malfunction code or protection code.

    No display when the unit stops.

    9.3 Protection

    9.3.1 Three Minutes Delay at restart for compressor.

    9.3.2 Temperature protection of compressor top.

    25

  • 7/29/2019 Guia Service

    29/60

    T1-24

    If the temperature of compressor top is too high (higher than 115C and the Over-load Protector is cut, the unit

    stops. When the Over-load Protector restores and closes (lower than 100C), the compressor will restart) in this

    case the compressor is restricted by Three Minutes Delay protection.

    9.3.3 Inverter module Protection

    Inverter module Protection itself has a protection function against current, voltage and temperature. If these

    protections happened, the corresponding code will display on indoor unit LED.

    9.3.4 Sensor protection at open circuit and breaking disconnection

    9.3.5 Fan Speed is out of control.

    When Indoor Fan Speed is too low (lower than 300RPM for 60 seconds), the unit stops and LED displays

    failure information and cant return to normal operation automatically.

    9.3.6 Cross Zero signal error warning.

    If there are 20 alternations of Cross Zero signals are incorrect, the unit stops and LED displays failure

    information. After resuming, the motor rotates again. The spacing of Cross Zero signal is 6-13ms.

    9.3.7 Indoor fan delayed at start function9.3.8 For all modes, when the units are turned on, the indoor fan can operate 10 seconds after the action of louver.

    9.3.9 Compressor preheating function.

    1) Preheating permitting condition:

    If T4 (outdoor ambient temperature)

  • 7/29/2019 Guia Service

    30/60

    T=(roomt

    emp)(settingTemp)

    3.53.0-0.5-1.0

    AB

    H

    When the machine is running and T(=room temp. setting temp.) changes, the frequency of compressor willrise or descend a grade (7 minutes after starting).After start, if T stays in a zone for 3 minutes, the frequency will change as follows:Zone A : Current frequency rises a grade till the maximum grade.Zone B: Elevate or keep or descend the frequency of compressor.Zone H: Compressor stops after running at the minimum frequency for 60 minutes or T is less than -2C.

    9.5.2 Indoor heat exchanger anti-freezing function.If T2 is lower than 0C, the compressor stops and resumes when T2>5C.

    9.5.3 Outdoor unit current control in cooling mode(refer to the parameter table)

    outdoorunitcurrent I3COOL

    I2COOLI1COOL

    comp. pause

    freq. descends if curr. rises;

    freq. remains if curr. descendsrunning normally

    Remark:Model I1COOL I2COOL I3COOLiDWM26 4.5 A 5.5 A 6.5 AiDWM50 5.2 A 6.4 A 7.5 AiDWM50 9.5A 10.5A 13A

    iDWM70 11A 12A 13A

    9.5.4 Rating capacity test function1) Set the indoor unit with remote controller as: high fan, 17 in cooling mode, then press TURBO button on

    controller 6 times or more within 10 seconds(make sure indoor unit receives these signals), the machine

    will turn into rating capacity test mode, the buzzer will make a di sound for 2 seconds continuously. Also,

    indoor fan will change to rating speed; the frequency of compressor will be fixed as rating value. Any

    condition of above is not satisfied, the machine cannot be turned into rating capacity test mode.2) The machine will quit from the rating capacity test mode if running for 5 hours or changing fan speed

    or setting temperature.

    9.5.5 Turbo function(press the TURBO button on remote controller)

    1) Elevate current frequency to a higher grade.

    2) Indoor fan turns to turbo speed.

    3) After running for 30 minutes the machine will turn back to previous setting mode.

    9.5.6 Indoor fan operation rule.

    27

  • 7/29/2019 Guia Service

    31/60

    1) In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto.2) Auto fan in cooling mode acts as follow:

    C

    4.03.01.51.0

    9.5.7 Condenser high temperature protection function(in cooling and drying mode)If T3>60C for 5 seconds, compressor will stop immediately, and the machine will not resume until T3

  • 7/29/2019 Guia Service

    32/60

    9.7 Heating mode9.7.1 Indoor fan action:

    1) Anti-cold-wind function.

    Evaporatortemp

    44383734332417

    Setting fan speedLow fan

    BreezeSuper breezeFan stop

    2) If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127 seconds

    with breeze. During this period, anti-cold-wind is disabled. After this, anti-cold wind function is available.

    3) If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and anti-cold-wind is

    disabled.

    9.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is

    preferential. Auto fan action in heating mode.

    T=(roomt

    emp)

    (settingTemp)

    2.52.01.51.0

    lowmedium

    high9.7.3 After starting, the operation frequency of compressor submits to following rule:

    Th=(roomt

    emp)(settingTemp)Tcon

    5.04.51.00.5

    Remark: Tcon can be changed among 0, -2, 4C, the default is 0C1) When the machine runs, if Th stays in a zone for 3 minutes, action of frequency is as follows:

    Zone A: Elevate current frequency one grade, and not stop until the maximum grade.

    Zone B: Elevate or keep or descend current frequency.Zone H: Compressor stops after running with F1 (min. Frequency) for 60 minutes or when Th>6C.

    C

    C

    C

    H

    B

    A

    29

  • 7/29/2019 Guia Service

    33/60

    1) Temperature difference (Tcon) choice (Heating mode)

    After power on, the machine will self-diagnose and if there aren't any J1 and J2 jump wires (see indoor unit wiring diagram),

    Tcon will be set as 0C. It is recommended to keep J1 and J2 at factory settings.Changing these settings should be

    carried out only by a qualified technician.

    J1 On On Off Off

    J2 On Off On Off

    Tcon (C) 0 -4 -2 0

    9.7.4 Outdoor unit current control in heating mode.

    current

    I3HEAT

    unit

    I2HEAT

    outdoor

    I1HEATRemark:

    Model I1HEAT I2 HEAT I3 HEAT

    iDWM26 5.2 A 6.4 A 7.5 A

    iDWM35 5.2 A 6.4 A 7.5 AiDWM50 9.5A 10.5A 13A

    iDWM70 11A 12A 13A

    9.7.5 Indoor heat exchanger high temperature protection.

    If T2>60C, the compressor will stop and not resume until T20C,

    When the units are running, if any one of the following two items are satisfied the units start defrosting:

    a) The unit runs with T3

  • 7/29/2019 Guia Service

    34/60

    9.7.7 Defrosting action.F8

    compressor onoff

    4-way valveonoff

    outdoor fan onoff

    indoor fan onoff

    indoor fan breeze 10s60s

    70sno longer than 10 minutes 30s

    9.7.8 Rating capacity test function.1) Set the indoor unit with remote controller as: high fan, 30C in heating mode, then press TURBO button on

    controller 6 times or more within 10 seconds(make sure indoor unit receives these signals), the machine

    will turn into rating capacity test mode, the buzzer will make a di sound for 2 seconds continuously. Also,

    indoor fan will change to rating speed; the frequency of compressor will be fixed as rating value. Any

    condition of above is not satisfied, the machine cannot be turned into rating capacity test mode.2) The machine will quit from the rating capacity test mode if running for 5 hours or changing fan speed or

    setting temperature.

    9.7.9 Turbo function in heating mode. (press the TURBO button on remote controller)

    1) Elevate current frequency (excluding F8) to a higher grade. If indoor fan is in low speed or pause caused

    by defrosting or anti-cold-wind function, frequency of compressor will not be elevated one grade until these

    limit has been released.

    2) Indoor fan changes to turbo speed and anti-cold-wind function is valid.

    3) After running for 30 minutes the machine will turn back to previous setting mode.

    9.8 Auto Mode Function

    9.8.1 This mode can be chosen with remote controller and the setting temperature can be changed between 17~30 C.In auto mode, the machine will choose cooling, heating or fan-only mode according to T (T =T1-Ts).

    T=T1-Ts Running modeT>1C Cooling

    -1C T1C Fan-onlyT

  • 7/29/2019 Guia Service

    35/60

    9.8.4 If the setting temperature is modified, the machine will rechoose running function.9.9 Forced operation function9.9.1 Forced cooling and auto function can becarried out with a touch button on the indoor unit. In these two modes,

    the machine can be changed by remote controller to any other mode at any moment.

    9.9.2 When the machine is off, pressing the touch button will carry the machine to forced auto mode, after this, if

    pressing the button once again within 5 seconds, the machine will turn into forced cooling mode. In forced auto,

    forced cooling or any other operation mode, pressing touch button will turn off the machine. In forced operation,

    remote control is available.

    9.9.3 In forced operation mode, all general protections are available.

    9.9.4 In forced cooling mode, after running for 30 minutes the machine will turn to normal auto mode which has a

    setting temperature of 24C.

    9.9.5 The action of forced auto mode is the same as normal auto mode which has a temperature of 24C.

    9.10 Action of 4-way valveIn heating, fan-only, standby or turning off mode 4-way valve is off, while in cooling or drying mode 4-way valve

    is on. If the machine changes operation mode from cooling or drying mode to some other mode, 4-way valve will

    be delayed off 2 minutes after compressor stop. For defrosting, please refer to the section defrosting mode.

    9.11 Two speeds outdoor fan function9.11.1 Outdoor fan starts at the same time with compressor, but stops 30 seconds later after compressor stop.

    9.11.2 Outdoor fan action in heating mode (including heating in auto mode).

    outdoortemperature

    1715

    lowhigh

    outdoorfanspeed

    outdoortemperature

    2220

    highlow

    outdoorfanspeed

    Outdoor fan action in heating mode

    (including heating in auto mode). Outdoor fan action in cooling & drying mode(including cooling in auto & forced mode).9.11.3 Outdoor fan action in cooling & drying mode (including cooling in auto & forced mode).

    Please refer to the pic. above.9.12 Timer function9.12.1 Timing range is 24 hours, and the minimum resolution is 15 minutes.

    9.12.2 Timer on. After turning off, the machine will turn on automatically when reaching the setting time.

    9.12.3 Timer off. After turning on, the machine will turn off automatically when reaching the setting time.

    9.12.4 Timer on/off. After turning off, the machine will turn on automatically when reaching the setting on time, and

    then turn off automatically when reaching the setting off time.

    9.12.5 Timer off/on. After turning on, the machine will turn off automatically when reaching the setting off time, and

    then turn on automatically when reaching the setting on time.

    9.12.6 The tolerance of timer is 1 minute per hour.

    32

  • 7/29/2019 Guia Service

    36/60

    9.13 Sleep function mode9.13.1 Operation time in sleep mode is 7 hours. After 7 hours the machine quits this mode and turns off.

    9.13.2 In cooling, heating or auto mode sleep function is available.

    9.13.3 Operation process in sleep mode is as follow:

    1) After pressing ECONOMIC or SLEEP button on controller, the machine will turn into sleep mode.

    2) When cooling the setting temperature rises by 1C (be lower than 30C) every one hour; 2 hours later the

    rising stops and indoor fan is fixed as low speed.

    3) When heating, the setting temperature descends by 1C (be lower than 30C) every one hour; 2 hours later

    the descending stops and indoor fan is fixed as low speed, and anti-cold wind is available.

    9.13.4 If user uses timer on function in sleep mode, sleep function will pause and not resume until reaches the setting

    on time.

    9.13.5 When user uses timer off function in sleep mode (or sleep function in timer off mode), if the timing time is less

    than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing time is more than 7

    hours, the machine will not stop until reaches the setting off time in sleep mode.

    9.14 Auto-Restart functionThe indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In case

    of a sudden power failure, the module restores the setting conditions before the power failure. The unit will

    resume the previous operation setting (not including Swing function) automatically after 3 minutes when power

    returns.

    33

  • 7/29/2019 Guia Service

    37/60

    10. TroubleshootingSafetyBecause there are capacitors in PCB and relative circuit in outdoor unit, even ifthe power supply is shut down,

    electricity power still is kept in capacitors.Do not forget to discharge the electricity power in capacitor.

    Electrolytic Capacitors(HIGH VOLTAGE! CAUTION!)

    Bulb (25-40W)

    Discharge

    34

  • 7/29/2019 Guia Service

    38/60

    10.1 Indoor Unit Error DisplayDisplay LED STATUSE0 EEPROM parameter errorE1

    Indoor / outdoor units communication protection

    E2 Zero-crossing signal errorE3 Fan speed out of controlE5 Open or short circuit of outdoor temperature sensor (T4)E6 Open or short circuit of room (T1) or evaporator temperature sensor (T2)P0 Outdoor PCB protectionP1 Over voltage or too low voltage protectionP2 Temperature protection of compressor top.P4 Inverter compressor drive error

    Note:E2 & E3 is not applicable for the model iDWM70.E4 & P3: Reserved function

    35

  • 7/29/2019 Guia Service

    39/60

    Reconnect and test again

    Correct the connectionReplace outdoor PCB

    Be sure the power supply is good

    and correct the connection

    Indoor PCB is defective. Replace

    the indoor PCB.

    10.2 Diagnosis and Solution10.2.1 E0 (EEPROM parameter error) error diagnosis and solution

    Circuit or software error on indoor PCB Replace indoor PCB

    10.2.2 E1 (indoor / outdoor units communication protection) error diagnosis and solutionDisconnect the power supply, after 1 minute,

    connect the power supply, turn on the unit

    with remote controllerDoes the unit work normally?

    NOCheck the wiring between

    indoor and outdoor unit. Is

    the connection of L, N, S

    and GND good?Is the GND connection on

    outdoor PCB good?Yes

    Is the LED4(red) on

    outdoor PCB bright and

    LED1(yellow) blinking?No

    The power supply for outdoor

    PCB is fail. Check the wiring

    on outdoor PCB comparing

    with wiring plate. Is the

    connection good?No

    10.2.3 E2 (zero-crossing signal error) diagnosis and solutionIs power supply and

    connection of

    connectors good?YES

    NO

    Yes

    Yes

    NO

    Replace indoor PCB

    and repower on. Is

    the failure cleared?

    Replace indoor PCB

    36

  • 7/29/2019 Guia Service

    40/60

    10.2.4 E3 (indoor fan speed out of control) diagnosis and solutionIs the indoor fan motor

    connector and

    connection good?YES

    Is voltage being applied to

    the fan motor?(range 90v-160v between

    mid pin and N on CN1NO

    NO Repair the connector andreconnect

    YES Indoor PCB is defective.Replace the indoor PCB.

    Replace the indoor

    fan motor

    10.2.5 E5 (Open or short circuit of outdoor temperature sensor(T4)) diagnosis and solution.Is the outdoor temperature

    sensor(T4) connector and

    connection good?YES

    Replace the sensor(T4) and

    check if E5 display again?

    NO Repair the connector andreconnect

    YESReplace outdoor e-box

    10.2.6 E6 (open or short circuit of room (T1) or evaporator temperature sensor(T2)) diagnosis and solution.Is the indoor temperature (T1)and evaporator sensor(T2) NO Repair the connector andconnector and connection

    reconnectgood?

    YESYESReplace the sensors (T1, T2)

    Replace the indoor PCBand check if E6 display again?

    10.2.7 P0 (Outdoor PCB protection) diagnosis and solution.Is all connections on

    PCB and between PCB

    and compressor good?YES

    Replace the outdoor PCB

    and then repower on. Is

    the failure cleared?

    NO Repair or correct theconnector or connection.

    NOCheck the compressor

    37

  • 7/29/2019 Guia Service

    41/60

    10.2.8 P1 (over voltage or too low voltage protection) diagnosis and solution.Is the power supply good?

    YESNO Be sure the power supply is

    normal when using the unitsReplace the outdoor e-box.

    10.2.9 P2 (temperature protection of compressor top) diagnosis and solution.NO NODoes compressor

    operate? Is the connectiongood? Reconnect and retest.

    YESIs refrigerant

    circulation

    volume normal?NO

    Charge refrigerant

    Is abnormality

    the same after

    gas charging?

    YESNOIs protector

    normal?YES

    Check the outdoor

    main PCB. Is there

    some problem?YES

    Replace the protector.

    Replace the outdoor PCB.

    NO

    10.2.10 P4 (inverter compressor drive error) diagnosis and solution.Is the connection of

    NOcompressor good? Is thewiring sequence right? Thevoltage range proper?

    Check refrigerant system (such

    as clogging of capillary, etc)

    Reconnect and retryYES

    Replace the outdoor E-box.

    If the problem comes to NOagain, check coil resistance

    Replace inverter compressorof inverter compressor, is it0.71ohm?

    38

  • 7/29/2019 Guia Service

    42/60

    10.3 Key Part Checking

    10.3.1 Compressor checking

    Measure the resistance value of each winding by using the multi-meter.

    Model: DA108X1C-20FZ3 (For Models iDWM25, iDWM35)

    Position Resistance Value

    Blue-Red 0.71 (20C)Blue-Black

    Red-Blue

    Model: C-6RVN93H0N (For Model iDWM50)Position Resistance Value

    Blue-Red 0.668 (25C)Blue-Black

    Red-Blue

    Model: C-6RZ146H1A (For Model iDWM70)Position Resistance Value

    Blue-Red 0.452 (25C)Blue-Black

    Red-Blue

    10.3.2 Outdoor Fan Motor

    Measure the resistance value of each winding by using the multi-meter.

    Model: YDK24-6G (For Model iDWM26, iDWM35)

    Position Resistance Value

    Black-Red 435 (20C)

    Blue-Red 213 (20C)

    Yellow-Blue 138 (20C)

    Model: YDK53-6F (For Model iDWM50)Position Resistance Value

    Black-Red 87.8 (20C)Red-Yellow 141.5 (20C)

    Model: YDK53-6N (For Model iDWM70)

    Position Resistance Value

    Black-Red 113 (20C)

    Red-Yellow 193 (20C)

    10.3.3 Indoor Fan Motor

    Measure the resistance value of each winding by using the multi-meter.

    Model: RPG20D (For Model iDWM26, iDWM35)

    Position Resistance Value

    Black-Red 415 8% (20C)

    White-Black 290 8% (20C)

    Model: RPG28D (For Model iDWM50)Position Resistance Value

    Black-Red 220 8% (20C)

    White-Black 330 8% (20C)

    Model: YDK50-4E (For Model iDWM70)Position Resistance Value

    Black-Red 206 (20C)

    Red-Yellow 99 (20C)

    iDWM26, 35, 50

    iDWM70

    39

  • 7/29/2019 Guia Service

    43/60

    10.3.4 Step Motor

    Measure the resistance value of each winding by using the multi-meter.

    Model: MP2835 (For Model iDWM26, iDWM35)

    Model: MP2423B (For Model iDWM50)

    Model: MP2423 (For Model iDWM70)

    10.3.5 Temperature

    Sensors.

    Room temperature sensor (T1),

    Indoor coil temperature sensor (T2),

    Outdoor coil temperature sensor (T3),

    Outdoor ambient temperature sensor (T4),

    Compressor discharge temperature sensor (Te).

    Measure the resistance value of each sensor by using the multi-meter.

    Some frequently-used R-T data for T1, T2, T3 and T4 sensor:

    Temperature (C) 5 10 15 20 25 30 40 50 60

    Resistance Value (K) 26.9 20.7 16.1 12.6 10 8 5.2 3.5 2.4

    Some frequently-used R-T data for Te sensor:

    Temperature (C) 5 15 25 35 60 70 80 90 100Resistance Value(K)

    141.6 88 56.1 36.6 13.8 9.7 6.9 5 3.7

    K

    C

    Position Resistance Value

    Blue - Red

    2007% (25)Pink - Orange

    Pink - Yellow

    Yellow - Red

    9(10)

    7(8)

    1(2)

    3(4)

    5(6)

    40

  • 7/29/2019 Guia Service

    44/60

    11.1ID

    WMG26-INDOOR

    SAG

    ECODE-85620

    1

    2

    3

    6

    8

    5

    7

    9

    12

    17

    18

    13

    14

    15

    16

    19

    20

    21

    25

    23

    24

    28

    26

    27

    22.

    222.

    1

    22.

    3

    22.

    4

    22.

    52

    2.

    6

    22.

    7

    22

    4

    10

    11

    22.

    8

    41

    11. Explosion Diagram

  • 7/29/2019 Guia Service

    45/60

    No.

    SageCode

    SageDescription

    BOMCode

    Qty

    Remark

    1

    868024

    FRNTPANLASYG26-35

    201130490085

    1

    2

    868027

    AIRFILTRG26-35

    201130490113

    2

    3

    868010

    AIRCLEANRG26-35-50

    201130100212

    1

    4

    868011

    AIRCLNHLDG26-35-50

    201130100217

    1

    5

    868086

    DISPBOXASSYG26-35

    203332390256

    1

    6

    868032

    WINDCOVREPG26-35

    201130490186

    1

    7

    868028

    SCREWC

    APG26-35

    201130490115

    3

    8

    868046

    FRAMEPNLASYG26-35

    201132590058

    1

    9

    868023

    BAFFLEG26-35-50-70

    201130490002

    1

    10

    868029

    AIROTFRMASYG26-35

    201130490117

    1

    11

    868075

    LOUVERMOTORG26-35

    202400200006

    1

    12

    868007

    DRAINHOSEG26-35-70

    201130000011

    1

    13

    868020

    BREAKWATERG26-35-50

    201130310350

    1

    14

    868062

    EVAPASSYG26

    201532390080

    1

    15

    868025

    MOTORCOVG26-35

    201130490106

    1

    16

    868077

    MOTORG26-35

    202400300215

    1

    17

    868082

    BEARINGHOLDRG26-35

    202730100201

    1

    18

    868001

    CROSSFLWF

    ANG26-35

    201100200100

    1

    19

    868030

    CHASSISG26-35

    201130490118

    1

    20

    868008

    CNPIPECLPG26-35-50

    201130100204

    1

    21

    868054

    INSTALLPLATEG26-35

    201230390006

    1

    22

    868085

    ELECTRLBXINDRG26

    203332390107

    1

    22.1

    868031

    EPARTBOXCOVG26-35

    201130490184

    1

    22.2

    868073

    WIREJOINTG26-35-50

    202301450119

    1

    22.3

    868080

    IDTSENG26-35-50-70

    202432390005

    1

    22.4

    868009

    PWRCORDCLAMPG26-35

    201130100209

    1

    22.5

    868071

    EVTSENG26-35-50-70

    202301300080

    1

    22.6

    868057

    MNCTRLBRD+CHIPG26

    201332390051

    1

    22.7

    868026

    EPARTBOXG26-35

    201130490108

    1

    22.8

    868069

    TRANFRMRG26-35

    202300900537

    1

    23

    868091

    REMCTRLG26-35-50-70

    203355090395

    1

    R07

    24

    868053

    CTRLHLDG26-35-50-70

    201155090087

    1

    25

    868081

    SEALG26-35-50-70

    202720090001

    1

    26

    868003

    CNTRWTRG26-35-50-70

    201101020011

    1

    27

    868065

    NUTTLMA01G26-35-50

    201600320000

    1

    28

    868066

    NUTTLMB02G26-70

    201600320001

    1

    42

    iDWMG26-INDOOR

  • 7/29/2019 Guia Service

    46/60

    SageCode

    857621

    11.2IDWM

    Z26-OUTDOOR

    43

  • 7/29/2019 Guia Service

    47/60

    No.

    SageCode

    SageDescription

    BOMcode

    Qty

    Remark

    1

    868201

    TEMPSENSRZ26-35

    202301300160

    1

    2

    868109

    REARNETZ26-35

    2011374G0003

    1

    3

    868170

    CNSRCOILASSYZ26-35

    201537390033

    1

    4

    868214

    PIPETPSENZ26-35-50

    202440500004

    1

    5

    868124

    VALVEPLATEZ26-35

    201235120614

    1

    6

    868137

    BASEPANASSYZ26-35

    201237590027

    1

    7

    868104

    BIGHANDLEZ26-35

    201135000005

    1

    8

    868105

    WATRCOLLECTRZ26-35

    201135270201

    1

    9

    868126

    RGHTCLAPBRDZ26-35

    201235270204

    1

    10

    868120

    CLPCAPCZ26-35-50-70

    201200100002

    1

    11

    868211

    CAPTRCOMPRZ26-35

    202401090055

    1

    12

    868135

    PARTNPLATEAZ26-35

    201237590008

    1

    13

    868133

    FRONTPANELZ26-35

    201237400029

    1

    14

    868110

    FRONTNETZ26-35

    201137590000

    1

    15

    868134

    MTRMNTGBRKTZ26-35

    201237500005

    1

    16

    868101

    AXIALFLWF

    ANZ26-35

    201100300502

    1

    17

    868132

    LEFTSUPPTRZ26-35

    201237400028

    1

    18

    868119

    SMALLHDLEZ26-35-50

    201150290006

    1

    19

    868127

    TOPCOVASSYZ26-35

    201235270249

    1

    20

    868208

    MOTORZ26-35

    202400400477

    1

    21

    868195

    REACTORZ26-35-50-70

    202301000819

    1

    22

    868125

    INDUCTCOVRZ26-35

    201235250802

    1

    23

    868196

    REACTORZ26-35

    202301000820

    1

    24

    868217

    ELECBOXASSYZ26-35

    203337390121

    1

    24.1

    868130

    EPRTBXZ26-35-50-70

    201237300171

    1

    24.2

    868205

    RADIATORZ26-35

    202301900068

    1

    24.3

    868129

    EPARTBCOVZ26-35-50

    201237300162

    1

    24.4

    868164

    MAINCTRLBRDZ26-35

    201337390032

    1

    24.5

    868108

    HLDEPTZ26-35-50-70

    201137300162

    1

    25

    868216

    BRDTERMASSYZ26-35

    203337390043

    1

    25.1

    868203

    WIREJOINTZ26-35-50

    202301450113

    1

    25.2

    868103

    WSHRJNTZ26-35-50-70

    201135000004

    1

    25.3

    868122

    WIRECLAMPZ26-35-50

    201219900001

    1

    25.4

    868136

    BOARDOFTERMZ26-35

    201237590009

    1

    26

    868184

    LIQVALVEASSYZ26

    201637390335

    1

    26.1

    868182

    LIQUIDVALVEZ26-35

    201600740523

    1

    27

    868183

    GASVALVEASSYZ26

    201632390037

    1

    27.1

    868174

    4WAYVALVEZ26-35

    201600670003

    1

    27.2

    868177

    GASPIPEVALVEZ26

    201600720200

    1

    28

    868200

    DISCHTPSENSZ26-35

    202301300159

    1

    29

    868167

    COMPRESSORZ26-35

    201400620600

    1

    DA

    108X1C-20FZ3

    44

    iDWMZ

    26-OUTDOOR

  • 7/29/2019 Guia Service

    48/60

    Sag

    eCode857622

    11.3ID

    WMG35-INDOOR

    1

    2

    3

    6

    8

    5

    7

    9

    12

    17

    18

    13

    14

    15

    16

    19

    20

    21

    25

    23

    24

    28

    26

    27

    22.

    222.

    1

    22.

    3

    22.

    4

    22.

    522.

    6

    22.

    7

    22

    4

    10

    11

    22.

    8

    45

  • 7/29/2019 Guia Service

    49/60

    N

    o.

    SageCode

    SageDescription

    BOMCode

    Qty

    Remark

    1

    868024

    FRNTPANLASYG26-35

    201130490085

    1

    2

    868027

    AIRFILTRG26-35

    201130490113

    2

    3

    868010

    AIRCLEANRG26-35-50

    201130100212

    1

    4

    868011

    AIRCLNHLDG26-35-50

    201130100217

    1

    5

    868086

    DISPBOXASSYG26-35

    203332390256

    1

    6

    868032

    WINDCOVREPG26-35

    201130490186

    1

    7

    868028

    SCREWC

    APG26-35

    201130490115

    3

    8

    868046

    FRAMEPNLASYG26-35

    201132590058

    1

    9

    868023

    BAFFLEG26-35-50-70

    201130490002

    1

    1

    0

    868029

    AIROTFRMASYG26-35

    201130490117

    1

    1

    1

    868075

    LOUVERMOTORG26-35

    202400200006

    1

    1

    2

    868007

    DRAINHOSEG26-35-70

    201130000011

    1

    1

    3

    868020

    BREAKWATERG26-35-50

    201130310350

    1

    1

    4

    868063

    EVAPASSYG35

    201532590050

    1

    1

    5

    868025

    MOTORCOVG26-35

    201130490106

    1

    1

    6

    868077

    MOTORG26-35

    202400300215

    1

    1

    7

    868082

    BEARINGHOLDRG26-35

    202730100201

    1

    1

    8

    868001

    CROSSFLWF

    ANG26-35

    201100200100

    1

    1

    9

    868030

    CHASSISG26-35

    201130490118

    1

    2

    0

    868008

    CNPIPECLPG26-35-50

    201130100204

    1

    2

    1

    868054

    INSTALLPLATEG26-35

    201230390006

    1

    2

    2

    868087

    DRAINHOSEG26-35-70

    203332590029

    1

    22

    .1

    868031

    EPARTBOXCOVG26-35

    201130490184

    1

    22

    .2

    868073

    WIREJOINTG26-35-50

    202301450119

    1

    22

    .3

    868080

    IDTSENG26-35-50-70

    202432390005

    1

    22

    .4

    868009

    PWRCORDCLAMPG26-35

    201130100209

    1

    22

    .5

    868071

    EVTSENG26-35-50-70

    202301300080

    1

    22

    .6

    868058

    MNCTRLBRD+CHIPG35

    201332590036

    1

    22

    .7

    868026

    EPARTBOXG26-35

    201130490108

    1

    22

    .8

    868069

    TRANFRMRG26-35

    202300900537

    1

    2

    3

    868091

    REMCTRLG26-35-50-70

    203355090395

    1

    R07

    2

    4

    868053

    CTRLHLDG26-35-50-70

    201155090087

    1

    2

    5

    868081

    SEALG26-35-50-70

    202720090001

    1

    2

    6

    868003

    CNTRWTRG26-35-50-70

    201101020011

    1

    2

    7

    868065

    NUTTLMA01G26-35-50

    201600320000

    1

    2

    8

    868067

    NUTTLMC03G35-50

    201600320002

    1

    46

    iDWMG35-INDOOR

  • 7/29/2019 Guia Service

    50/60

    Sage

    Code

    857623

    11.4IDW

    MZ35-OUTDOOR

    47

  • 7/29/2019 Guia Service

    51/60

    No.

    SageCode

    SageDescription

    BOMcode

    Qty

    Re

    mark

    1

    868201

    TEMPSENSRZ26-35

    202301300160

    1

    2

    868109

    REARNETZ26-35

    2011374G0003

    1

    3

    868170

    CNSRCOILASSYZ26-35

    201537390033

    1

    4

    868214

    PIPETPSENZ26-35-50

    202440500004

    1

    5

    868124

    VALVEPLATEZ26-35

    201235120614

    1

    6

    868137

    BASEPANASSYZ26-35

    201237590027

    1

    7

    868104

    BIGHANDLEZ26-35

    201135000005

    1

    8

    868105

    WATRCOLLECTRZ26-35

    201135270201

    1

    9

    868126

    RGHTCLAPBRDZ26-35

    201235270204

    1

    10

    868120

    CLPCAPCZ26-35-50-70

    201200100002

    1

    11

    868211

    CAPTRCOMPRZ26-35

    202401090055

    1

    12

    868135

    PARTNPLATEAZ26-35

    201237590008

    1

    13

    868133

    FRONTPANELZ26-35

    201237400029

    1

    14

    868110

    FRONTNETZ26-35

    201137590000

    1

    15

    868134

    MTRMNTGBRKTZ26-35

    201237500005

    1

    16

    868101

    AXIALFLWF

    ANZ26-35

    201100300502

    1

    17

    868132

    LEFTSUPPTRZ26-35

    201237400028

    1

    18

    868119

    SMALLHDLEZ26-35-50

    201150290006

    1

    19

    868127

    TOPCOVASSYZ26-35

    201235270249

    1

    20

    868208

    MOTORZ26-35

    202400400477

    1

    21

    868196

    REACTORZ26-35

    202301000820

    1

    22

    868125

    INDUCTCOVRZ26-35

    201235250802

    1

    23

    868195

    REACTORZ26-35-50-70

    202301000819

    1

    24

    868217

    ELECBOXASSYZ26-35

    203337390121

    1

    2

    4.1

    868130

    EPRTBXZ26-35-50-70

    201237300171

    1

    2

    4.2

    868205

    RADIATORZ26-35

    202301900068

    1

    2

    4.3

    868129

    EPARTBCOVZ26-35-50

    201237300162

    1

    2

    4.4

    868164

    MAINCTRLBRDZ26-35

    201337390032

    1

    2

    4.5

    868108

    HLDEPTZ26-35-50-70

    201137300162

    1

    25

    868216

    BRDTERMASSYZ26-35

    203337390043

    1

    2

    5.1

    868203

    WIREJOINTZ26-35-50

    202301450113

    1

    2

    5.2

    868103

    WSHRJNTZ26-35-50-70

    201135000004

    1

    2

    5.3

    868122

    WIRECLAMPZ26-35-50

    201219900001

    1

    2

    5.4

    868136

    BOARDOFTERMZ26-35

    201237590009

    1

    26

    868186

    LIQVALVEASSYZ35

    201637590287

    1

    2

    6.1

    868182

    LIQUIDVALVEZ26-35

    201600740523

    1

    27

    868185

    GASVALVEASSYZ35

    201637590195

    1

    2

    7.1

    868174

    4WAYVALVEZ26-35

    201600670003

    1

    2

    7.2

    868178

    GASPIPEVALVEZ35

    201600720201

    1

    28

    868200

    DISCHTPSENSZ26-35

    202301300159

    1

    29

    868167

    COMPRESSORZ26-35

    201400620600

    1

    DA108X

    1C-20FZ3

    48

    iDWMZ

    35-OUTDOOR

  • 7/29/2019 Guia Service

    52/60

    11.5IDWM

    G50-INDOOR

    SageCode857624

    1

    2

    4

    7

    5

    6

    8

    17

    18

    9

    10

    15

    16

    20

    21

    22

    23.

    1

    23.

    2

    23.

    3

    23.

    4

    23.

    5

    23.

    6

    24

    25

    26

    27

    29

    28

    23

    14

    23.

    7

    23.

    9

    19

    3

    11

    12

    13

    23.

    8

    49

  • 7/29/2019 Guia Service

    53/60

    No.

    SageCode

    SageDescrip

    tion

    BOMCode

    Qty

    Remarks

    1

    868018

    FRONTPANELASSYG50

    201130290255

    1

    2

    868015

    AIRFILTRG

    50

    201130290162

    2

    3

    868010

    AIRCLEANRG2

    6-35-50

    201130100212

    1

    3.1

    868011

    AIRCLNHLDG2

    6-35-50

    201130100217

    1

    4

    868084

    DISPLAYBOXAS

    SYG50

    203330290120

    1

    5

    868019

    WINDCOVRREP

    AIRG50

    201130290288

    1

    6

    868014

    SCREWC

    AP

    G50

    201130290161

    3

    7

    868016

    PANELFRAMAS

    SYG50

    201130290164

    1

    8

    868017

    AIROUTFRAMASSYG50

    201130290253

    1

    9

    868076

    LOUVERMOTO

    RG50

    202400200025

    1

    10

    868004

    DRAINHOSE

    G50

    201101020014

    1

    11

    868021

    SENSORCLAMP

    G50-70

    201130390070

    1

    12

    868023

    BAFFLEG26-35

    -50-70

    201130490002

    1

    13

    868020

    BREAKWATERG

    26-35-50

    201130310350

    1

    14

    868064

    EVAPASSYG50

    201532790029

    1

    15

    868048

    MOTORCOV

    G50

    201132800003

    1

    16

    868078

    MOTORG50

    202400300415

    1

    17

    868033

    FIXINGBRDBEARG50

    201130510515

    1

    18

    868083

    BEARINGHOLD

    RG50

    202730500001

    1

    19

    868000

    CROSSFLOWF

    ANG50

    201100200014

    1

    20

    868047

    CHASSISG

    50

    201132800001

    1

    21

    868008

    CNPIPECLPG2

    6-35-50

    201130100204

    1

    22

    868055

    INSTALLNPLAT

    EG50

    201232790008

    1

    23

    868088

    ELECTRLBXIN

    DRG50

    203332790024

    1

    23.1

    868070

    TRANFRMRG

    50-70

    202300900573

    1

    23.2

    868013

    EPARTBOXCOVRG50

    201130210070

    1

    23.3

    868073

    WIREJOINTG26-35-50

    202301450119

    1

    23.4

    868022

    WIRECLAMP1G50

    201130400042

    1

    23.5

    868080

    IDTSENG26-35

    -50-70

    202432390005

    1

    23.6

    868071

    EVTSENG26-35-50-70

    202301300080

    1

    23.7

    868059

    MNCTRLBRD+C

    HIPG50

    201332790042

    1

    23.8

    868006

    WIRECLAMP2G50

    201121990012

    1

    23.9

    868012

    ELECCONTRLB

    OXG50

    201130210069

    1

    24

    868091

    REMCTRLG26-3

    5-50-70

    203355090395

    1

    25

    868053

    CTRLHLDG26-3

    5-50-70

    201155090087

    1

    26

    868081

    SEALG26-35-50-70

    202720090001

    1

    27

    868003

    CNTRWTRG26-35-50-70

    201101020011

    1

    28

    868065

    NUTTLMA01G2

    6-35-50

    201600320000

    1

    29

    868067

    NUTTLMC03G

    35-50

    201600320002

    1

    50

    iDWMG50-INDOOR

  • 7/29/2019 Guia Service

    54/60

    11.6

    ID

    WMZ50-OUTDOOR

    SageCode857625

    51

  • 7/29/2019 Guia Service

    55/60

    No.

    SageCode

    SageDescription

    BOMcode

    Qty

    Re

    mark

    1

    868117

    REARNETZ50

    2011481G0001

    1

    2

    868199

    TEMPSENSRZ50-70

    202301300057

    1

    3

    868171

    CNSRCOILASSYZ50

    201537790025

    1

    4

    868214

    PIPETPSENZ26-35-50

    202440500004

    1

    5

    868123

    VALVEPLATEZ50

    201235000018

    1

    6

    868141

    BASEPANASSYZ50

    201237790020

    1

    7

    868120

    CLPCAPCZ26-35-50-70

    201200100002

    1

    8

    868212

    CAPTRCOMPRZ50-70

    202401090057

    1

    9

    868116

    BIGHANDLEZ50

    201145500003

    1

    10

    868142

    RGHTCLAPBRDZ50

    20123799G001

    1

    11

    868106

    WATERCOLLECTRZ50

    201135290005

    1

    12

    868155

    FTRGHTCLPBDASZ50

    2012481G0001

    1

    13

    868139

    PARTNPLATEASSYZ50

    201237790004

    1

    14

    868153

    FRONTPANELZ50

    201248100071

    1

    15

    868112

    FRONTNETZ50-70

    201138090000

    1

    16

    868148

    MTRMNTGBRKTZ50

    201245220804

    1

    17

    868194

    FOAMMOTORHOLDRZ50

    202245500001

    1

    18

    868115

    AXIALFLOWF

    ANZ50

    201145500002

    1

    19

    868152

    LEFTSUPPTRZ50

    201248100070

    1

    20

    868209

    ASYNCHMTRIRONZ50

    202400410652

    1

    21

    868154

    SUPPBRDMTRHLDZ50

    201248100076

    1

    22

    868119

    SMALLHDLEZ26-35-50

    201150290006

    1

    23

    868156

    TOPCOVASSYZ50

    2012481G0035

    1

    24

    868195

    REACTORZ26-35-50-70

    202301000819

    1

    25

    868140

    2COVREACTFILTZ50

    201237790013

    1

    26

    868197

    REACTORZ50-70

    202301000834

    1

    27

    868219

    ELECBOXASSYZ50

    203337790029

    1

    27.1

    868130

    EPRTBXZ26-35-50-70

    201237300171

    1

    27.2

    868206

    RADIATORZ50

    202301900075

    1

    27.3

    868129

    EPARTBCOVZ26-35-50

    201237300162

    1

    27.4

    868165

    MAINCTRLBRDZ50

    201337790004

    1

    27.5

    868108

    HLDEPTZ26-35-50-70

    201137300162

    1

    28

    868218

    BOARDTERMASSYZ50

    203337790021

    1

    28.1

    868203

    WIREJOINTZ26-35-50

    202301450113

    1

    28.2

    868103

    WSHRJNTZ26-35-50-70

    201135000004

    1

    28.3

    868122

    WIRECLAMPZ26-35-50

    201219900001

    1

    28.4

    868138

    BOARDOFTERMZ50

    201237790003

    1

    29

    868187

    LIQVALVEASSYZ50

    201637790048

    1

    29.1

    868181

    LIQUIDVALVEZ50

    201600740522

    1

    30

    868188

    GASVALVEASSYZ50

    201637790327

    1

    30.1

    868175

    4WAYVALVEZ50

    201600690011

    1

    30.4

    868176

    GASPIPEVALVEZ50

    201600720194

    1

    31

    868202

    DISTPSENSASZ50-70

    202301310068

    1

    32

    868168

    COMPRESSORZ50

    201400710680

    1

    C-6RV

    N93H0N

    33

    868213

    HEATBELTCOMPZ50-70

    202403100501

    1

    52

    iDWMZ

    50-OUTDOOR

  • 7/29/2019 Guia Service

    56/60

    11.7IDW

    MG70-INDOOR

    Sage

    Code857628

    53

  • 7/29/2019 Guia Service

    57/60

    No.

    SageCode

    SageDescription

    BOMCode

    Qty

    Rema

    rk

    1

    868051

    FRONTPANELASSYG70

    201133190012

    1

    2

    868041

    AIRFILTRG70

    201130790202

    2

    3

    868090

    DISPLAYBOXASSYG70

    203333190024

    1

    4

    868039

    AIRCLEANRG70

    201130790130

    1

    4.1

    868038

    AIRCLEANHLDRG70

    201130790129

    1

    5

    868040

    SCREWC

    APG70

    201130790131

    5

    6

    868052

    PANELFRAMEG70

    201133190015

    1

    7

    868045

    AIROUTFRAMASSYG70

    201130790206

    1

    8

    868074

    LOUVERMOTORG70

    202400200004

    1

    9

    868007

    DRAINHOSEG26-35-70

    201130000011

    1

    10

    868021

    SENSORCLAMPG50-70

    201130390070

    1

    11

    868023

    BAFFLEG26-35-50-70

    201130490002

    1

    12

    868080

    IDTSENG26-35-50-70

    202432390005

    1

    13

    868061

    EVAPASSYG70

    201530790075

    1

    14

    868071

    EVTSENG26-35-50-70

    202301300080

    1

    15

    868042

    WATERPROOFBRDG70

    201130790203

    1

    16

    868035

    MOTORSMALLCOVG70

    201130790124

    1

    17

    868036

    MOTORCOVG70

    201130790127

    1

    18

    868079

    MOTORG70

    202400410648

    1

    19

    868037

    BASEFORMOTORG70

    201130790128

    1

    20

    868005

    BEARINGHOLDRG70

    201101090004

    1

    21

    868002

    CROSSFLOWF

    ANG70

    201100290011

    1

    22

    868044

    CHASSISASSYG70

    201130790205

    1

    23

    868043

    CRNRBRDCHASSISG70

    201130790204

    1

    24

    868056

    INSTALLNPLATEG70

    201233190002

    1

    25

    868089

    ELECTRLBXINDRG70

    203333090141

    1

    25.1

    868050

    EPARTBOXG70

    201133090113

    1

    25.2

    868049

    EPARTBOXCOVRG70

    201133090112

    1

    25.3

    868060

    MNCTRLBRD+CHIPG70

    201333090163

    1

    25.4

    868070

    TRANFRMRG50-70

    202300900573

    1

    25.5

    868072

    WIREJOINTG70

    202301420101

    1

    25.6

    868034

    POWERCORDCLAMPG70

    201130790120

    1

    26

    868091

    REMCTRLG26-35-50-70

    203355090395

    1

    R07

    27

    868053

    CTRLHLDG26-35-50-70

    201155090087

    1

    28

    868066

    NUTTLMB02G26-70

    201600320001

    1

    29

    868068

    COPPERNUTG70

    201600320003

    1

    30

    868081

    SEALG26-35-50-70

    202720090001

    1

    31

    868003

    CNTRWTRG26-35-50-70

    201101020011

    1

    54

    iDWMG70-INDOOR

  • 7/29/2019 Guia Service

    58/60

    11.8

    IDW

    MZ70-OUTDOOR

    Sage

    Code

    857629

    55

  • 7/29/2019 Guia Service

    59/60

    No.

    S

    ageCode

    SageDescription

    BOMcode

    QtyR

    emark

    No.

    SageCode

    SageD

    escription

    BOMcode

    Qty

    Remark

    1

    868118

    REARNETZ70

    201148200000

    1

    28

    868159

    TOPCO

    VASSYZ70

    2012482G0013

    1

    2

    868199

    TEMPSENSRZ50-7

    0

    202301300057

    1

    29

    868161

    INDUCT

    COVRZ70

    201250200303

    1

    3

    868111

    WATERPROOFBRDZ

    70

    201137990000

    1

    30

    868163

    PROTBRD

    INDUCTZ70

    201250200306

    1

    4

    868172

    CNSRCOILASSYZ7

    0

    201538090030

    1

    31

    868198

    REAC

    TORZ70

    202301040055

    1

    5

    868215

    PIPETEMPSENSRZ

    70

    202441200200

    1

    32

    868162

    HLDRBRD

    INDUCTZ70

    201250200305

    1

    6

    868151

    VALVEPLATEZ70

    201245370923

    1

    33

    868221

    ELECBO

    XASSYZ70

    203338090086

    1

    7

    868146

    BASEPANASSYZ7

    0

    20123809G003

    1

    33.1

    868207

    RADIA

    TORZ70

    202301900084

    1

    8

    868120

    CLPCAPCZ26-35-50-

    70

    201200100002

    1

    33.2

    868131

    EPARTBO

    XCOVRZ70

    201237300173

    1

    9

    868212

    CAPTRCOMPRZ50-70

    202401090057

    1

    33.3

    868166

    MAINCT

    RLBRDZ70

    201338090004

    1

    10

    868113

    BIGHANDLEZ70

    201145320903

    1

    33.4

    868108

    HLDEPT

    Z26-35-50-70

    201137300162

    1

    11

    868107

    WATERCOLLECTRZ

    70

    201135490001

    1

    33.5

    868130

    EPRTBX

    Z26-35-50-70

    201237300171

    1

    12

    868128

    RGHTCLAPBRDZ7

    0

    201235490023

    1

    34

    868220

    BOARDTE

    RMASSYZ70

    203338090035

    1

    13

    868150

    FTRGHTCLPBDASZ

    70

    201245320946

    1

    34.1

    868204

    WIREJOINTZ70

    202301450118

    1