Planilla de calculo de malla a tierra

7
SITIO : EL VINCULO I.- MEDICION DE RESISTIVIDAD DE SUELO FECHA : 22/02/2006 INSTRUMENTO : MEGABRAS MTD SERIE 20 KW METODO : SISTEMA DE 4 ELECTRODOS, CONFIGURACION SCHLUMBERGER DATOS MEDIDOS: MEDICION a n n a L Re [ohm] Pa [ohm] 1 1 1 1.0 0.6 18.86 6.52 2 1 2 2.0 0.8 5.44 6.67 3 1 4 4.0 4.5 3.42 214.88 4 1 6 6.0 6.5 0.46 60.70 5 1 8 8.0 8.5 0.15 33.93 6 1 10 10.0 10.5 0.09 31.10 7 1 12 12.0 12.5 0.05 24.50 8 1 15 15.0 15.5 0.03 22.62 9 1 18 18.0 18.5 0.02 21.49 10 1 23 23.0 23.5 0.015 26.01 11 1 28 28.0 28.5 0.01 25.51 RESULTADOS DE MEDIDA CURVA PATRON A -9 (0,5) 43.08 CAPA ESPESOR [m] RESISTIVIDAD [ohm-m] 1 E1 = 0.8 P1 = 50 2 E2 = 0.5 P2 = 50.00 3 E3 = 10E+06 P3 = 10E+06

description

calculo malla a tierra

Transcript of Planilla de calculo de malla a tierra

Hoja1SITIO :EL VINCULOI.-MEDICION DE RESISTIVIDAD DE SUELOFECHA: 22/02/2006INSTRUMENTO: MEGABRAS MTD SERIE 20 KWMETODO: SISTEMA DE 4 ELECTRODOS, CONFIGURACION SCHLUMBERGERDATOS MEDIDOS:MEDICIONann aLRe [ohm]Pa [ohm]1111.00.618.866.522122.00.85.446.673144.04.53.42214.884166.06.50.4660.705188.08.50.1533.93611010.010.50.0931.10711212.012.50.0524.50811515.015.50.0322.62911818.018.50.0221.491012323.023.50.01526.011112828.028.50.0125.51RESULTADOS DE MEDIDACURVA PATRONA -9 (0,5)43.08CAPAESPESOR [m]RESISTIVIDAD [ohm-m]1E1 =0.8P1 =502E2 =0.5P2 =50.003E3 =10E+06P3 =10E+06

Hoja3MEMORIA CALCULO MALLA BT1.-CALCULO RESISTIVIDAD EQUIVALENTE DEL TERRENO, DE ACUERDO AL MODELODE YAKOBS, DONDE:DONDE:CON:DATOS INICIALESSUPERFICIE DISPONIBLE [m2]S67.5PROF. ENTERRAMIENTO [m]b0.8RADIO CIRCULO EQUIV. [m]r4.635ro220.846q250.3884q2ro24201.561LUEGOh1 =0.8h12 =0.64u1 =71.874h2 =1.3h22 =1.69u2 =72.924h3 =1.00E+07h32 =1.00E+14u3 =1.00E+14ENTONCESvo2 =20.846F1 =0.1450.020.0840.0016816691v12 =20.410F2 =0.2290.020.7710.0154267807v22 =19.756F3 =1.0000.00000010.7710v32 =0.0000.0171084498CON ESTO LA RESISTIVIDAD EQUIVALENTE ES:r eq =58.45ohm-mt2.-CALCULO DE LA RESISTENCIA DE LA MALLA BT SEGN METODO DE SCHWARZ15CARACTERISTICAS MALLA PROPUESTA1.5LADO MAYOR [m]A12LADO MENOR [m]B4.560PROFUNDIDAD DE ENTERRAMIENTOb0.84849.5DIAMETRO CONDUCTOR [m]dc0.00941/013.5109.5LARGO CONDUCTOR MALLA [m]L61.561.5N ELECTRODOSN2SEGN SCHWARZ67.5DONDEYLUEGOK1 =1.089YK2 =4.861ENTONCES LA RESISTENCIA DE LA MALLA ES:Rpt =3.19[ohm]Rpt (tratamiento ericogel) =1.91417996833.-CALCULO DE CORTOCIRCUITO MONOFASICOCORTOCIRCUITO MONOFASICO:(1)DONDE, PARA SECUENCIA CERO:YDONDE:R =3.19ohmRESISTENCIA MALLA TIERRAIcc1f =220[A]CORRIENTE CCTO MONOFASICO (POR EMPRESA ELECTRICA)Icc3f =380[A]CORRIENTE CCTO TRIFASICO (POR EMPRESA ELECTRICA)V =13200[V]VOLTAJE DE LINEA (POR EMPRESA ELECTRICA)ENTONCES:x1 =20.055x2 =20.055x0 =63.812REEMPLAZANDO EN (1)Icc1f =219[A]LA CORRIENTE DE CORTOCIRCUITO REAL SERAIg = Icc1f * FD * FcDONDEFD =1FACTOR DE DECREMENTO PATA t =0,5 SegFc =1FACTOR DE CRECIMIENTO PARA t =0,5 SegLUEGO:Ig =219[A]CON ESTO:4.-DETERMINACION SECCION MINIMA CONDUCTOR MALLADE ACUERDO A ECUACION DE ONDERDONKS:DONDEI=219[A]CORRIENTE CCTO REAL RMSt=0.5[seg]TIEMPO DESPEJETm=1083CT ADMISIBLE MAXIMA POR CONDUCTORTa=40CT AMBIENTEA=CMSECCION DEL CONDUCTOR EN CMREEMPLAZANDO TENEMOS QUEA =1075CMA =1.08MCMPERO1 MCM =0.5067[mm2]A =0.54[mm2]5.-CALCULO VALORES MAXIMOS DE POTENCIALES TOLERADOSYDONDEVmp =VOLTAJE CONTACTOVpp =VOLTAJE PASOCs =FACTOR DE CORRECCIONDONDEbo =0.1[mt]ESPESOR RECUBRIMIENTO(GRAVILLA)rs =50[ohm-mt]RASISTIVIDAD 1 CAPArg =3000[ohm-mt]RESISTIVIDAD RECUBRIMIENTOt =0.5[seg]TIEMPO DESPEJE FUSIBLEa =0.106[mt]EQUIVALENCIA PIE A ESFERA DE RADIO aREEMPLAZANDO TENEMOS QUECs =0.659LUEGO:Vmp =651[V]Vpp =2122[V]6.-CALCULO POTENCIALES MALLA PROPUESTAYDONDEDONDEL =61.5[mt]LARGO CONDUCTOR MALLAn =5.5N CONDUCTORES LADO MENORD =6[mt]SEPARACION CONDUCTORES LADO MENORho =1[mt]REEMPLAZANDOKii =0.418Kn =1.341Km =0.888Ki =1.602Ks =0.294LUEGOVmp =296[V]Vpp =98[V]296