Presentation IEC Rey-An Moreno
-
Upload
rey-an-a-moreno -
Category
Documents
-
view
224 -
download
0
Transcript of Presentation IEC Rey-An Moreno
-
8/17/2019 Presentation IEC Rey-An Moreno
1/53
BY: REYNALDO A. MORENO
-
8/17/2019 Presentation IEC Rey-An Moreno
2/53
-
8/17/2019 Presentation IEC Rey-An Moreno
3/53
• To gather and protect the control and protectivedevices together with electrical and mechanical
connections against external influences.• To inform the end-user on the state of his
installation.• To protect the switchboard user against the main
risk of accidents (direct contact protection,indirect contact protection and fire risk).
• To evolve with the activity
What is a switchboard used for ?
-
8/17/2019 Presentation IEC Rey-An Moreno
4/53
The LV electrical switchboard has to be safe
and available
• It is a question of balance between:
–
the needs of safety and availability – the constraints of reliability and maintenability of
the installation.Safety
Maintenability
Reliability Availability
-
8/17/2019 Presentation IEC Rey-An Moreno
5/53
-
8/17/2019 Presentation IEC Rey-An Moreno
6/53
Ingress protection of enclosures
-
8/17/2019 Presentation IEC Rey-An Moreno
7/53
-
8/17/2019 Presentation IEC Rey-An Moreno
8/53
-
8/17/2019 Presentation IEC Rey-An Moreno
9/53
Power Distribution System
• The most common IT-system• Limited earth fault current – depending on capacitance in the cabling system• Alarm in case of an earth fault• Ideal for emergency power and important consumers with need for continuous
operation• To be used in UPS-systems
Isolated IT-system
-
8/17/2019 Presentation IEC Rey-An Moreno
10/53
Power Distribution System
• The miniature circuit breaker with integrated earth fault tripping is
functioning very well in a fully insulated IT-system!
Isolated IT-system (230 V)
-
8/17/2019 Presentation IEC Rey-An Moreno
11/53
Power Distribution System
• Earth fault current calculated to maximum 100 A
• Consumers will be tripped in case of an earth fault
Impedance earthed IT-system
-
8/17/2019 Presentation IEC Rey-An Moreno
12/53
Power Distribution System
• Two voltage levels in one system!
• 400/230 V are the most common voltages
• Separate N- and PE-conductors
• Consumers will be tripped in case of an earth fault
• EMC Performance - Excellent
Directly earthed TN-S system
-
8/17/2019 Presentation IEC Rey-An Moreno
13/53
-
8/17/2019 Presentation IEC Rey-An Moreno
14/53
-
8/17/2019 Presentation IEC Rey-An Moreno
15/53
Signal Classes
• Class 1 - Mains power lines, power circuits with ahigh di/dt, switch-mode converters, power regulation
• Class 2 - Relay contacts.• Class 3 - Digital circuits (HF switching).• Class 4 - Analogue input/output circuits (low-level
measurements, active sensor supply circuits)
-
8/17/2019 Presentation IEC Rey-An Moreno
16/53
Protective Sheaths
-
8/17/2019 Presentation IEC Rey-An Moreno
17/53
Routing of Cables
-
8/17/2019 Presentation IEC Rey-An Moreno
18/53
Routing of Cables
-
8/17/2019 Presentation IEC Rey-An Moreno
19/53
Routing of Cables
• Spare cable conductors shall either be terminated orinsulated.
-
8/17/2019 Presentation IEC Rey-An Moreno
20/53
• Power and low level apparatus shall be physically separated andcables segregation and distances between power and sensitivecables shall also be respected as shown on the figure:
-
8/17/2019 Presentation IEC Rey-An Moreno
21/53
Power Circuits
-
8/17/2019 Presentation IEC Rey-An Moreno
22/53
Screening of horizontally installed busbars
-
8/17/2019 Presentation IEC Rey-An Moreno
23/53
Termination
-
8/17/2019 Presentation IEC Rey-An Moreno
24/53
Conductor Ends (Termination)
-
8/17/2019 Presentation IEC Rey-An Moreno
25/53
Conductor Ends (Termination)
-
8/17/2019 Presentation IEC Rey-An Moreno
26/53
-
8/17/2019 Presentation IEC Rey-An Moreno
27/53
Earthing Connections and Conductors
Minimum cross-section of Earthing conductors
Arrangement of earthconductor
Cross-section Q ofassociated currentcarrying conductor(one phase or pole)(mm2)
Minimum cross-section of earthconductor
2. Uninsulated earthconductor in cable for fixedinstallation, being laid underthe cable's lead sheath,armour or copper braid andin metal-to-metal contactwith this.
Q ≤ 2.5 1 mm2
2.5 < Q ≤ 6 1.5 mm2
6 < Q Not permitted
3. Separately installed earthconductor for fixedinstallation
Q < 2.5 Same as current-carrying conductorsubject to minimum 1.5 mm2 forstranded earthing connection or 2.5mm2 for unstranded earthingconnection
-
8/17/2019 Presentation IEC Rey-An Moreno
28/53
Cabinet Cabling
-
8/17/2019 Presentation IEC Rey-An Moreno
29/53
Cabinet Cabling
-
8/17/2019 Presentation IEC Rey-An Moreno
30/53
Enclosure
-
8/17/2019 Presentation IEC Rey-An Moreno
31/53
Arrangement of Earth Bus-bar
• IE Bar should be isolated from the panel
-
8/17/2019 Presentation IEC Rey-An Moreno
32/53
Arrangement of Earth Bus-bar
IEC 61892-6 (2007):4.1.3 quotes:“Earth bars, when provided, shall
be located in front of equipmentand junction boxes to allow foreasy access for usage, inspectionand maintenance. All earth barsand terminals shall be visible andpossible to be checked also after
termination of cables.”
-
8/17/2019 Presentation IEC Rey-An Moreno
33/53
Arrangement of Earth Bus-bar for MCC
Install the complete cable rightup to the level of the
actual starter, and terminate thebraiding and/or earthconductor to the vertical subearth bar at this level !
-
8/17/2019 Presentation IEC Rey-An Moreno
34/53
Earth Terminations
IEC 61892-6 (2007):4.1.3 quotes:“Separate connections shall beused for each individual earthconductor.”
-
8/17/2019 Presentation IEC Rey-An Moreno
35/53
Equipment Protective Earthing
• Suitable star washers and conductor terminals shallbe used, so that a reliable contact is ensured.
-
8/17/2019 Presentation IEC Rey-An Moreno
36/53
Equipment Protective Earthing
• The earthing of the cable itself may be carried out by fixing thecable to the hull constructions, or to parts that are welded or
riveted to the hull constructions (metal to metal without paint orcoating), by corrosion resistant clamps or metal clips.
-
8/17/2019 Presentation IEC Rey-An Moreno
37/53
Marking and Nameplate
-
8/17/2019 Presentation IEC Rey-An Moreno
38/53
Marking and Nameplate
-
8/17/2019 Presentation IEC Rey-An Moreno
39/53
Marking and Nameplate
-
8/17/2019 Presentation IEC Rey-An Moreno
40/53
Clearance and Creepage Distances
Clearance Clearance is the shortest distance between two conductive parts measured through air.Creepage Creepage is the shortest distance between two conductive parts measured along a surface.
-
8/17/2019 Presentation IEC Rey-An Moreno
41/53
“Type tested assemblies” and “Partly type tested assemblies”
a) Electrical low voltage assemblies constructed and tested in accordance withIEC 60092-302, item 7.1.2.101
(referring to IEC 61439-1) are accepted as long as the following conditionsare met:— minimum clearance distance shall be 8 mm, minimum creepage distanceshall be 16 mm— the assembly has been type tested with impulse voltage test in accordancewith IEC 61439-1
— maximum operating temperature of busbars shall be documented to beacceptable with respect to fixingmaterials and internal temperature by a full current type test— maximum temperature rise at termination points for external cables shallbe 60ºC — such assemblies shall not be installed in machinery space category “A”.
-
8/17/2019 Presentation IEC Rey-An Moreno
42/53
-
8/17/2019 Presentation IEC Rey-An Moreno
43/53
HAZARDOUS AREAS
• Zone 0 – Area in which an explosive gas atmosphere is presentcontinuously or for long periods.
– Certified safe for Intrinsic safety Ex-ia
• Zone 1 – Area in which an explosive gas atmosphere is likely tooccur in normal operation.
• Zone 2 – Area in which an explosive gas atmosphere is not likelyto occur in normal operation and, if it does occur, islikely to do so infrequently and will exist for a shortperiod only.
– certified safe for Zone 1 and Zone 2 application.—Ex-n standard
—Minimum of IP45
-
8/17/2019 Presentation IEC Rey-An Moreno
44/53
Ex Protection According to Zones
Zone 2 Zone 1 Zone 0Ex d (flameproof) Yes Yes No
Ex e (increased safety) Yes Yes No
Ex i (intrinsic safe) Yes Yes Yes
Ex p (pressurised) Yes Yes No
Ex n Yes No No
Ex s (special protection) Yes Yes Yes
Ex m (moulded) Yes Yes No
Ex q Yes Yes No
Ex o Yes Yes No
-
8/17/2019 Presentation IEC Rey-An Moreno
45/53
HAZARDOUS AREAS
-
8/17/2019 Presentation IEC Rey-An Moreno
46/53
HAZARDOUS AREAS
-
8/17/2019 Presentation IEC Rey-An Moreno
47/53
HAZARDOUS AREAS
• Ex-i circuits
– All intrinsic safe circuits shall have a safety barrier in form of a zener
barrier or galvanic isolation certified safe for the application in front of thecircuit part going into hazardous areas.
– A circuit in which no spark or any thermal effect produced is capable ofcausing ignition of a given explosive atmosphere
-
8/17/2019 Presentation IEC Rey-An Moreno
48/53
HAZARDOUS AREAS
• Ex-i circuits
– All intrinsic safe circuits shall have a safety barrier in form of a zener
barrier or galvanic isolation certified safe for the application in front of thecircuit part going into hazardous areas.
• Exi barrier and circuit(s)
must be sufficiently separatedfrom other circuits
-
8/17/2019 Presentation IEC Rey-An Moreno
49/53
Corresponding Values for NEMA-Type and IP-rating
-
8/17/2019 Presentation IEC Rey-An Moreno
50/53
Cable types, Cabling and Termination
• All cables installed in hazardous areas shall have an outer non-metallicimpervious sheath.
•
Power and signal cables shall have a metallic braiding or armourbetween conductors and the non-metallic impervious sheath in thefollowing zones and areas:
— zone 0
— zone 1
-
8/17/2019 Presentation IEC Rey-An Moreno
51/53
-
8/17/2019 Presentation IEC Rey-An Moreno
52/53
The tests of standard IEC 60439-1
There are two type of tests:
• 7 type tests are performed by the manufacturer on one or severalconfigurations: – n°1 temperature rise limits – n°2 dielectric properties – n°3 short-circuit withstand – n°4 protective circuit effectiveness –
n°5 clearances and creepage distances
– n°6 mechanical operation – n°7 degree of protection.
• 3 routine tests are performed by the panelbuilder on each particularswitchboard:
– n°8 general inspection – n°9 insulation/dielectric test – n°10 protection measures.
-
8/17/2019 Presentation IEC Rey-An Moreno
53/53