Presentation IEC Rey-An Moreno

download Presentation IEC Rey-An Moreno

of 53

Transcript of Presentation IEC Rey-An Moreno

  • 8/17/2019 Presentation IEC Rey-An Moreno

    1/53

     

    BY: REYNALDO A. MORENO

  • 8/17/2019 Presentation IEC Rey-An Moreno

    2/53

     

  • 8/17/2019 Presentation IEC Rey-An Moreno

    3/53

    • To gather and protect the control and protectivedevices together with electrical and mechanical

    connections against external influences.• To inform the end-user on the state of his

    installation.• To protect the switchboard user against the main

    risk of accidents (direct contact protection,indirect contact protection and fire risk).

    • To evolve with the activity

    What is a switchboard used for ?

  • 8/17/2019 Presentation IEC Rey-An Moreno

    4/53

    The LV electrical switchboard has to be safe

    and available

    • It is a question of balance between:

     –

    the needs of safety and availability – the constraints of reliability and maintenability of

    the installation.Safety

    Maintenability

    Reliability  Availability

  • 8/17/2019 Presentation IEC Rey-An Moreno

    5/53

     

  • 8/17/2019 Presentation IEC Rey-An Moreno

    6/53

    Ingress protection of enclosures

  • 8/17/2019 Presentation IEC Rey-An Moreno

    7/53

     

  • 8/17/2019 Presentation IEC Rey-An Moreno

    8/53

     

  • 8/17/2019 Presentation IEC Rey-An Moreno

    9/53

    Power Distribution System 

    • The most common IT-system• Limited earth fault current – depending on capacitance in the cabling system• Alarm in case of an earth fault• Ideal for emergency power and important consumers with need for continuous

    operation• To be used in UPS-systems

    Isolated IT-system 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    10/53

    Power Distribution System 

    • The miniature circuit breaker with integrated earth fault tripping is

    functioning very well in a fully insulated IT-system!

    Isolated IT-system (230 V) 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    11/53

    Power Distribution System 

    • Earth fault current calculated to maximum 100 A

    • Consumers will be tripped in case of an earth fault

    Impedance earthed IT-system

  • 8/17/2019 Presentation IEC Rey-An Moreno

    12/53

    Power Distribution System 

    • Two voltage levels in one system!

    • 400/230 V are the most common voltages

    • Separate N- and PE-conductors

    • Consumers will be tripped in case of an earth fault

    • EMC Performance - Excellent

    Directly earthed TN-S system

  • 8/17/2019 Presentation IEC Rey-An Moreno

    13/53

     

  • 8/17/2019 Presentation IEC Rey-An Moreno

    14/53

     

  • 8/17/2019 Presentation IEC Rey-An Moreno

    15/53

     Signal Classes 

    • Class 1 - Mains power lines, power circuits with ahigh di/dt, switch-mode converters, power regulation

    • Class 2 - Relay contacts.• Class 3 - Digital circuits (HF switching).• Class 4 - Analogue input/output circuits (low-level

    measurements, active sensor supply circuits)

  • 8/17/2019 Presentation IEC Rey-An Moreno

    16/53

    Protective Sheaths 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    17/53

    Routing of Cables 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    18/53

    Routing of Cables 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    19/53

    Routing of Cables 

    • Spare cable conductors shall either be terminated orinsulated.

  • 8/17/2019 Presentation IEC Rey-An Moreno

    20/53

    • Power and low level apparatus shall be physically separated andcables segregation and distances between power and sensitivecables shall also be respected as shown on the figure:

  • 8/17/2019 Presentation IEC Rey-An Moreno

    21/53

    Power Circuits

  • 8/17/2019 Presentation IEC Rey-An Moreno

    22/53

    Screening of horizontally installed busbars

  • 8/17/2019 Presentation IEC Rey-An Moreno

    23/53

    Termination 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    24/53

    Conductor Ends (Termination) 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    25/53

    Conductor Ends (Termination) 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    26/53

     

  • 8/17/2019 Presentation IEC Rey-An Moreno

    27/53

    Earthing Connections and Conductors 

    Minimum cross-section of Earthing conductors

    Arrangement of earthconductor  

    Cross-section Q ofassociated currentcarrying conductor(one phase or pole)(mm2)  

    Minimum cross-section of earthconductor  

    2. Uninsulated earthconductor in cable for fixedinstallation, being laid underthe cable's lead sheath,armour or copper braid andin metal-to-metal contactwith this.

    Q ≤ 2.5  1 mm2

    2.5 < Q ≤ 6  1.5 mm2

    6 < Q Not permitted

    3. Separately installed earthconductor for fixedinstallation

    Q < 2.5 Same as current-carrying conductorsubject to minimum 1.5 mm2 forstranded earthing connection or 2.5mm2 for unstranded earthingconnection

  • 8/17/2019 Presentation IEC Rey-An Moreno

    28/53

    Cabinet Cabling 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    29/53

    Cabinet Cabling 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    30/53

    Enclosure

  • 8/17/2019 Presentation IEC Rey-An Moreno

    31/53

    Arrangement of Earth Bus-bar

    • IE Bar should be isolated from the panel

  • 8/17/2019 Presentation IEC Rey-An Moreno

    32/53

    Arrangement of Earth Bus-bar

    IEC 61892-6 (2007):4.1.3 quotes:“Earth bars, when provided, shall

    be located in front of equipmentand junction boxes to allow foreasy access for usage, inspectionand maintenance. All earth barsand terminals shall be visible andpossible to be checked also after

    termination of cables.” 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    33/53

    Arrangement of Earth Bus-bar for MCC

    Install the complete cable rightup to the level of the

    actual starter, and terminate thebraiding and/or earthconductor to the vertical subearth bar at this level !

  • 8/17/2019 Presentation IEC Rey-An Moreno

    34/53

    Earth Terminations

    IEC 61892-6 (2007):4.1.3 quotes:“Separate connections shall beused for each individual earthconductor.” 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    35/53

    Equipment Protective Earthing 

    • Suitable star washers and conductor terminals shallbe used, so that a reliable contact is ensured.

  • 8/17/2019 Presentation IEC Rey-An Moreno

    36/53

    Equipment Protective Earthing 

    • The earthing of the cable itself may be carried out by fixing thecable to the hull constructions, or to parts that are welded or

    riveted to the hull constructions (metal to metal without paint orcoating), by corrosion resistant clamps or metal clips.

  • 8/17/2019 Presentation IEC Rey-An Moreno

    37/53

    Marking and Nameplate 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    38/53

    Marking and Nameplate 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    39/53

    Marking and Nameplate 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    40/53

    Clearance and Creepage Distances 

    Clearance Clearance is the shortest distance between two conductive parts measured through air.Creepage Creepage is the shortest distance between two conductive parts measured along a surface.

  • 8/17/2019 Presentation IEC Rey-An Moreno

    41/53

    “Type tested assemblies” and “Partly type tested assemblies” 

    a) Electrical low voltage assemblies constructed and tested in accordance withIEC 60092-302, item 7.1.2.101

    (referring to IEC 61439-1) are accepted as long as the following conditionsare met:— minimum clearance distance shall be 8 mm, minimum creepage distanceshall be 16 mm— the assembly has been type tested with impulse voltage test in accordancewith IEC 61439-1

    — maximum operating temperature of busbars shall be documented to beacceptable with respect to fixingmaterials and internal temperature by a full current type test— maximum temperature rise at termination points for external cables shallbe 60ºC — such assemblies shall not be installed in machinery space category “A”. 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    42/53

     

  • 8/17/2019 Presentation IEC Rey-An Moreno

    43/53

    HAZARDOUS AREAS

    • Zone 0 – Area in which an explosive gas atmosphere is presentcontinuously or for long periods.

    –  Certified safe for Intrinsic safety Ex-ia

    • Zone 1 – Area in which an explosive gas atmosphere is likely tooccur in normal operation.

    • Zone 2 – Area in which an explosive gas atmosphere is not likelyto occur in normal operation and, if it does occur, islikely to do so infrequently and will exist for a shortperiod only.

    – certified safe for Zone 1 and Zone 2 application.—Ex-n standard

    —Minimum of IP45

  • 8/17/2019 Presentation IEC Rey-An Moreno

    44/53

    Ex Protection According to Zones 

    Zone 2 Zone 1 Zone 0Ex d (flameproof) Yes Yes No

    Ex e (increased safety) Yes Yes No

    Ex i (intrinsic safe) Yes Yes Yes

    Ex p (pressurised) Yes Yes No

    Ex n Yes No No

    Ex s (special protection) Yes Yes Yes

    Ex m (moulded) Yes Yes No

    Ex q Yes Yes No

    Ex o Yes Yes No

  • 8/17/2019 Presentation IEC Rey-An Moreno

    45/53

    HAZARDOUS AREAS

  • 8/17/2019 Presentation IEC Rey-An Moreno

    46/53

    HAZARDOUS AREAS

  • 8/17/2019 Presentation IEC Rey-An Moreno

    47/53

    HAZARDOUS AREAS

    • Ex-i circuits

    – All intrinsic safe circuits shall have a safety barrier in form of a zener

    barrier or galvanic isolation certified safe for the application in front of thecircuit part going into hazardous areas.

    – A circuit in which no spark or any thermal effect produced is capable ofcausing ignition of a given explosive atmosphere

  • 8/17/2019 Presentation IEC Rey-An Moreno

    48/53

    HAZARDOUS AREAS

    • Ex-i circuits

    – All intrinsic safe circuits shall have a safety barrier in form of a zener

    barrier or galvanic isolation certified safe for the application in front of thecircuit part going into hazardous areas.

    • Exi barrier and circuit(s)

    must be sufficiently separatedfrom other circuits

  • 8/17/2019 Presentation IEC Rey-An Moreno

    49/53

    Corresponding Values for NEMA-Type and IP-rating 

  • 8/17/2019 Presentation IEC Rey-An Moreno

    50/53

    Cable types, Cabling and Termination 

    • All cables installed in hazardous areas shall have an outer non-metallicimpervious sheath.

    Power and signal cables shall have a metallic braiding or armourbetween conductors and the non-metallic impervious sheath in thefollowing zones and areas:

    — zone 0

    — zone 1

  • 8/17/2019 Presentation IEC Rey-An Moreno

    51/53

     

  • 8/17/2019 Presentation IEC Rey-An Moreno

    52/53

    The tests of standard IEC 60439-1

    There are two type of tests:

    • 7 type tests are performed by the manufacturer on one or severalconfigurations:  – n°1 temperature rise limits – n°2 dielectric properties – n°3 short-circuit withstand – n°4 protective circuit effectiveness –

    n°5 clearances and creepage distances

     – n°6 mechanical operation – n°7 degree of protection. 

    • 3 routine tests are performed by the panelbuilder on each particularswitchboard: 

     – n°8 general inspection – n°9 insulation/dielectric test – n°10 protection measures.

  • 8/17/2019 Presentation IEC Rey-An Moreno

    53/53