PZ1000 Protección de Línea

download PZ1000 Protección de Línea

of 16

Transcript of PZ1000 Protección de Línea

  • DISTANCE PROTECTION

    PZ1000

  • The PZ1000 distance protection incorporates 4 MHO and/or quadran-

    gular trip characteristic zones and a 5th additional quadrangular zone

    for phase-phase and phase-earth faults plus pilot protection schemes,

    supervision alarms (pole by pole) and other functions, making it a top

    level distance protection.

    DESCRIPTION

    The PZ1000 relays are digital distance protection devices, specially

    suitable for primary protection of simple or double overhead transmis-

    sion and subtransmission line (high or medium voltage).

    Their advanced multiprocessor design and rapid signal proce-ssing

    algorithms make them fast acting and safe. They maintain the reliabi-

    lity and performance required to handle transmission and distribution

    networks.

    PZ1000 unit has a serial front communication port and can have up to

    two rear ports that allow:

    To link the units to a Protection and Control Integrated System.

    To access the status, historical data, and settings information, locally and / or remotely through telephone communications.

    It also has a third rear port for pilot protection, that allows the direct

    connection between two protections.

    INTRODUCTION

    FUNCTIONAL DESCRIPTION

    It also has a breaker failure protection unit and a single pole/triple pole

    recloser with up to 4 shots. Breaker monitor functions, number of trips,

    etc. work by pole by pole.

    2

    PZ1000 - 07/09

  • 3 Extension of zone 1

    Zone 4 is used for tripping and pilot protection

    The use of direct sequence voltage as polarization, produces abackward expansion of MHOs.

    Directional overcurrent units

    The PZ1000 has 2 additional protection units for phase directional

    overcurrent and for neutral directional overcurrent as backups for the

    main distance units, thus increasing the operational reliability of the

    relay.

    Overvoltage / Undervoltage units

    The PZ1000 has two three-phase voltage units: one for overvoltage and

    the other for undervoltage. Each phase is analysed separately.

    Homopolar overvoltage

    This function protects against faults to earth.

    Breaker failure protection

    It verifies the correct operation of a breaker when clearing a fault, cau-

    sing in other case, the trip of breakers of the positions needed to iso-

    late the fault.

    Stub protection

    This protects against faults between current transformers and line iso-

    lators configured with a breaker and a half scheme. It is an overcurrent

    unit which is activated when the line isolator is open.

    Thermal image

    It protects the line against thermal overloads, calculating the tempera-

    ture depending on the current and recent load conditions of the pro-

    tected unit.

    Current unbalance

    This device protects the line against unbalances produced in the

    current as consequence of power system anomalies or unbalance loads.

    This function is selected by setting as directional or no directional.

    All these characteristics are supported by other protection andsupervision functions which ensure the safe operation of the pro-

    tection device.

    This device is not recommended for short lines with CapacitiveVoltage Transformers (CVTs), being defined as short lines those

    whose SIR>10 if passive CVTs are used, and those whose SIR>4

    if active CVTs are used.

    SIR is the ratio between source impedance and the protected line

    impedance

    Negative sequence directional unit

    All impedance units are supervised by a negative sequence directional

    unit which indicates the direction of the fault.

    Pilot protection schemes

    Via communication with other terminals, the following protection sche-

    mes are possible:

    Staggered trip Permissive overreach: POTT Permissive underreach: PUTT Directional block: DCB Directional unblock: DCUB Permissive overreach 67N/67Q: POTT 67N/67QAdditional schemes:

    ECHO (for permissive schemes) Reverse direction blocking Weak infeed Direct transfer trip

    The pilot protection is executed via digital inputs and/or serial com-

    munication

    Enable by single-phase and phase-phase overcurrent

    This enables the distance unit if the current exceeds pre-set single-

    phase or phase-phase thresholds.

    Fuse failure

    This blocks the distance unit if the disappearance of any voltage is

    detected. The directional unit and/or the voltage unit can also be loc-

    ked depending on settings.

    Power swing

    This blocks the phase-phase distance units and gives power

    swing trip, if power unstable oscillation is detected.

    Load encroachment

    This blocks the phase-phase distance units if the impedance detected

    is within the load zone defined by the user.

    Switch-Onto-Fault

    This sets off an instant non directional three-phase trip when the switch

    closes on a fault in the line.

    DISTANCE PROTECTION

    OTHER PROTECTION FUNCTIONS

  • 4Breaker monitoring (for each pole)

    An event is generated when the kI meter for any phase exceeds thethreshold set.

    Trip and close circuit supervision 74TC/CC (for each pole)

    This detects any anomaly in the circuits with the switch open or closed.

    Excessive number of trips (for each pole)

    This generates an event and sends a signal to the control unit when the

    trips per phase exceed a preset number in a set time. It blocks the

    recloser when the set number is exceeded.

    Open phase alarm

    This sets off an alarm when an open phase is detected.

    CTs monitoring

    This generates an alarm when detecting a failure in a current input

    channel (only for models with In calculated in the own line).

    Single pole/triple pole recloser

    Programmable up to 4 shots

    The first shot is single/triple pole and the rest are triple pole

    Different times for each shot

    Operation counter for each shot

    Engaged/disengaged by setting, input and communications

    Syncrocheck

    This function compares the voltage signals for one phase (in modulus

    and argument) on both sides of the switch, and permits the switch to

    be closed when the pre-set conditions are met. It can be used for both

    manual and automatic closing.

    The angle difference is calculated compensating the breakers closing

    time.

    Dead line detection (DLD)

    This function detects the disconnected phases of a line, generating a

    signal.

    Self-testing

    The PZ1000 digital protection relay runs the following ongoing self-

    diagnostic checks:

    Software running

    Power supply voltage

    Hardware

    Picking-up of measurementsFailures detected by self-testing, are signalled by any of the double

    outputs (configurable).

    Pole discrepancy

    This unit checks the pole status concordance, causing three pole ope-

    ning after exceeding the set time with any pole in a status different

    from the rest.

    Programmable logic functions

    The user can configure up to 15 logic signals which can be assigned to

    output relays and LEDs via the SIPCON Protections software.

    MONITORING FUNCTIONS

    AUTOMATISMS AND COMANDS

  • 5Measurement

    The PZ1000 protection relay measures the following magnitudes in real

    time:

    Per phase and neutral currents

    Single and compound voltages per phase

    Frequency

    Active and reactive power levels and power factor

    Two-way energy

    Note1: Depending on models, equipments include external battery voltage mea-

    surement.

    Oscillograph data recorder

    Depending on the model, the non volatile memories of PZ1000units can store:

    20 records for 30 cycles 10 records for 60 cycles Each record comprises the samples from 8 analogue signals

    and the status of 16 selectable digital signals

    Tripping and preliminary start-up are configurable The disturbances are collected and exported in COMTRADE format.

    Fault records

    The last 9 faults are stored in the non volatile memory with the following data:

    Date and time of start-up, beginning and end of fault Pre-fault and fault levels of electrical parameters Duration and type of fault Units engaged Fault distance Trip zone and / or pilot trip

    Fault locator

    The fault locator processes the information gathered on each fault and

    calculates the distance to the fault location. The distance is given in km

    and it can be accesed via the display or the PC.

    Setting groups

    The unit has 4 setting groups. The active table selection can be made

    from the protections console or digital input activation.

    Event recording

    Queue of 200 events stored in non volatile memory can be recovered in

    text format on PC.

    Each event is accompanied by: Date and time of occurrence Descriptive code of event Level of electrical parameters (voltage and current) at the time ofoccurrence

    Historical reports

    A queue of 100 historical reports is stored in the non volatile memory,

    covering maximum and minimum average current and average voltage

    levels within a programmable time window.

    Time synchronization

    Via communications Via demodulated IRIG-B input

    The unit has clock with backup battery.

    Demand maximeter

    The unit stores the maximum current value, plus the time tag for the

    moment when it occurs.

    DATA ACQUISITION

  • 6The PZ1000 units have the following user communication elements:

    Display / keyboard

    Featuring:

    2 line, 16-character LCD

    16-key keyboard

    12 programmable LED indicators and 1 two-colour alarm LED

    4 push-button that can be deactivated by setting:

    This permits:

    Displaying of inputs, measurements, dates and times, statisticaldata and latest fault.

    Displaying and modification of settings and active table, assigna-tion of inputs, outputs and LEDs.

    Optionally, the unit can incorporate a frontal lid obtaining a IP of 54.

    Comunications

    The unit has:

    1 front serial port for local communication.

    2 rear serial ports (1 optional), for local and/or remote access toprotection and monitoring information.

    These outputs can provide all the information available on the protec-

    tion device, and can be used to modify settings of all types via SIPCON-

    protections software by INGETEAM T&D.

    The PZ1000 also features an optional rear series output for pilot pro-

    tection.

    In the PZ1000-AA and PZ1000-AB models IEC61850 PZ1000-AR and

    AS models have an Ethernet RJ45 or optical fibre port, a serial RS232

    PROCOME port and a serial DNP3.0 glass optical fibre port.The com-

    munications protocol for the first rear port (COM-1) is always Procome.

    The protocol of the second rear port (COM-2), if exists, is chosen by the

    user out of the next communications protocols: DNP or Procome.

    The third rear port uses a particular protocol with which teleprotection

    signals are sent and received.

    MAN-MACHINE INTERFACE

    INGETEAM T&D uses the SIPCON-Protections program, developed for

    PCs running under WINDOWS. This program allows clear, simple dialo-

    gue with the unit for access to the information stored in it and for

    adjustment.

    All configuration accesses are password protected to prevent tampering

    by unauthorised personnel.

    The outstanding features of the SIPCON-Protections program include

    the following:

    Automatic detection of the unit with which it is in dialogue.

    Unit status display via status screens

    Presentation and modification of settings

    Filling and presentation of all information stored by the relay:events, faults, historical data, oscilloscope readings, etc.

    SIPCON Protections is compatible with the software used in INGETE-

    AM T&Ds integrated protection and monitoring systems, and can be

    incorpora-ted into them as just one more function module.

    Breaker closure

    Breaker open

    Local / Remote

    Maneuver permission

    SOFTWARE

  • 7The illustration shows the application of a PZ1000 relay to protect over-

    head lines powered from both ends.

    In this protection scheme the pilot protection function is used.

    The illustration shows the application of a PZ1000 unit, to protect a

    breaker and a half scheme, in wich stub protection is used to protect

    against faults between current transformers and the isolator, when that

    isolator is open.

    The existence of three switches and the need for a breaker failure unit,

    recloser and syncrocheck for each of them, is handled by using INGE-

    TEAM T&Ds PL-70 single function devices:

    PL-70 SY: For the syncrocheck function.

    PL-70 FI: For the breaker failure function.

    PL-70 IT: For the recloser function.

    PROTECTION OF OVERHEAD LINES WITH POWER SUPPLY FROM BOTH ENDS

    STUB PROTECTION

    APPLICATIONS

  • 8DISTANCE PROTECTION (21)

    Settings Range Step

    Phase to earth Zones 1 to 4 () 0.01-300.00 0.01

    Phase to phase Zones 1 to 4 () 0.01-300.00 0.01

    Note: Settings for all 4 zones are independient

    MHO Reach

    Settings Range Step

    Phase to earth reactance Zones 1 to 5 () 0.01-300.00 0.01

    Phase to earth resistance Zones 1 to 5 () 0.01-300.00 0.01

    Phase to phase reactance Zones 1 to 5 () 0.01-300.00 0.01

    Phase to phase resistance Zones 1 to 5 () 0.01-300.00 0.01

    Note: Settings for all 4 zones are independient

    Settings Range StepZone 1 modulus 0.01-50.00 0.01

    Zone 1 angle (deg) 0-3590 10

    Zone 2 modulus 0.01-50.00 0.01

    Zone 2 angle (deg) 0-3590 10

    Other zones modulus 0.01-50.00 0.01

    Other zones angle (deg) 0-3590 10

    Mutual comp. zone 1 KMO modulus 0.01-300.00 0.01

    Mutual comp. zone 1 KMO angle 0-3590 10

    Mutual comp. zone 2 KMO modulus 0.01-300.00 0.01

    Mutual comp. zone 2 KMO angle 0-3590 10

    Mutual comp. other zones KMO modulus 0.01-300.00 0.01

    Mutual comp. other zones KMO angle 0-3590 10

    Cuadrilateral Reach

    Zero Sequence Compensation

    Settings Range StepZone 1 phase to earth (s) 0.0-100 0.01

    Zone 2 phase to earth (s) 0.0-100 0.01

    Zone 3 phase to earth (s) 0.0-100 0.01

    Zone 4 phase to earth (s) 0.0-100 0.01

    Zone 5 phase to earth (s) 0.0-100 0.01

    Zone 1 phase to phase (s) 0.0-100 0.01

    Zone 2 phase to phase (s) 0.0-100 0.01

    Zone 3 phase to phase (s) 0.0-100 0.01

    Zone 4 phase to phase (s) 0.0-100 0.01

    Zone 5 phase to phase (s) 0.0-100 0.01

    Timming

    Settings

    Phase to earth fault unitMHO, Cuadrilateral

    MHO & cuadrilateral, none

    Phase to phase fault unitMHO, Cuadrilateral

    MHO & cuadrilateral, none

    Single pole trip YES/NO

    General Setting

    Settings Range

    Zone 2

    No

    Fordward

    Backward with trip

    Backward without trip

    Zone 3

    No

    Fordward

    Backward with trip

    Backward without trip

    Zone 4

    No

    Backward with trip

    Backward without trip

    Zone 5

    No

    Fordward

    Backward

    Non-directional

    Settings Range Step

    Scheme type

    - Staggered trip

    - Permissive overreach

    - Permissive underreach

    - Directional block

    - Directional unblock

    - POTT 67N/ 67Q

    RTP input dropout time 0.00-1.00 0.01

    Block additional delay (s) 0.00-1.00 0.01

    Loss of guard delay 0.00-0.15 0.01

    ECHO enabled YES/NO

    Min. RTP delay fo ECHO (s) 0.00-10 0.01

    Reverse zone block enable YES/NO

    Reverse zone block delay 0.00-10 0.01

    Weak infeed enable YES/NO

    Direct trip enable YES/NO

    Pilot Protection Schemes

    Overreaching Direction

    Settings Range Step

    Enable

    YES

    NO

    YES + Z5

    YES - Z5

    Inner X (w) 0.01-300.00 0.01

    Inner R (w) 0.01-300.00 0.01

    Outer X (w) 0.01-300.00 0.01

    Outer R (w) 0.01-300.00 0.01

    Direct sequence threshold (A) (0.2-30) In 0.1

    Activation time (s) 0.01-50.00 0.01

    Imax threshold (A) (0.2-30) In 0.1

    I2/Imax ratio 10-50 0.1

    Z1, Z2, Z3, Z4, Z5 zone lockout YES/NO

    Power Swing (68PS)

    SETTINGS

    Settings Range StepEnable YES/NO

    Negative sequence threshold (V) 10.00-165.00 0.1

    Negative sequence threshold (A) (0.2-30) In 0.1

    Open Phase Alarm

    Settings Range StepEnable YES/NO

    I1 threshold (A) (0.2-30) In 0.1

    Impedance (w)

    (indepen. forward & reverse)0.01-300 0.1

    Angle + (gnd)

    (indepen. forward & reverse)0-3590 10

    Angle - (gnd)

    (indepen. forward & reverse)0-3590 10

    Load Enroachment (68LE)

    Settings Range Step

    Enable

    NO

    YES+Z2

    YES+Z5

    Positive sequence threshold (V) 10.00-165.00 0.1

    Positive sequence threshold (A) (0.2-30) In 0.1

    Switch-Onto-Fault

    Single-phase setting(4 tables)

    Minimum Maximum Step Notes

    Enable YES/NO

    Trip (A)0.5

    0.1

    150.0

    30.0

    0.1

    0.1

    For In= 5 A

    For In= 1 A

    Additional time(s) 0.00 10.00 0.01

    Two-phase setting (4tables)

    Minimum Maximum Step Notes

    Enable YES/NO

    Trip (A)0.5

    0.1

    150.0

    30.0

    0.1

    0.1

    For In= 5 A

    For In= 1 A

    Additional time(s) 0.00 10.00 0.01

    Settings Range StepEnable YES/NO

    Negative seq. threshold (V) 10.00-165.00 0.1

    Negative seq. threshold (A) (0.2-30) In 0.1

    Fuse Failure (68FF)

    Single Phase / Phase-Phase overcurrent

  • 9PHASE AND NEUTRAL DIRECTIONAL ELEMENTS (67)

    RECLOSER (79)Settings Range Step

    Reclose type selectionSingle pole, triple pole, single/triple

    pole, dependent

    Number of programmed shots 1-4 1

    Single pole 1st shot time (s) 0.1-20 0.1

    Triple pole 1st shot time (s) 0.1-20 0.1

    2nd shot time (s) 1-300 0.1

    3rd shot time (s) 1-300 0.1

    4th shot time (s) 1-300 0.1

    Sec. t. after single pole closing 1-300 0.1

    Sec. t. after triple pole closing 1-300 0.1

    Sec. t. after manual pole closing 1-100 0.1

    Synchronism time delay (s) 1-300 0.1

    CLOSURE PERMISSION AFTER TRIPSettings Range StepZone 1 YES/NO

    Zone 2 YES/NO

    Zone 3 YES/NO

    Zone 4 YES/NO

    Phase inst. YES/NO

    Phase timed YES/NO

    Neutral inst. YES/NO

    Neutral timed YES/NO

    Enable extension zone 1 YES/NO

    Ext. factor of zone 1 phase to phase fault 0.1-3 0.1

    Ext. factor of zone 1 phase to earth fault 0.1-3 0.1

    Inst. neutral locking after monopolar trip YES/NO

    1st timed neutral locking after monopolar trip YES/NO

    Inst. unbalance locking after monopolar trip YES/NO

    Timed unbalance locking after monopolar trip YES/NO

    Settings Range StepTimed enable NO, YES, YES + Dropout

    Timed pickup (0.2-4) In 0.1

    Response type

    Definite time

    Normal inverse IEC

    Very inverse IEC

    Extr. inverse IEC

    User IEC (mod.)

    Normal inverse ANSI

    Very inverse ANSI

    Extr. inverse ANSI

    User ANSI (mod.)

    Time index

    ANSI

    IEC-BSC

    0.5-30

    0.05-1.09

    0.1

    0.01

    Definite time 0-100 0.1

    Torque control YES/NO

    Instantaneous enable YES/NO

    Instantaneous pickup (0.2-30) In 0.1

    Instantaneous additional time 0-10 0.01

    Torque control YES/NO

    Negative/zero sequence angle 0-3590 10

    Directional lockout

    Vpol