Hoja11ra. PARCIAL DE INSTALACIONES ELECTRICAS 1 (PRACTICA)TEMA A1 PREGUNTA050-110 (a)a131piso183.96Sotanob152do piso183.9613espesor0.2sotano71.828TOTAL439.7495.76REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-110 (a)Area total = 439.74 m2050-200(a) (i)carga basica(ii)1ros 90m2 sera 2500 w250025003.8888888889sgtes 90m2 o fracc. sera 1000 w3.88640004000(iii)Calefaccion0otro calentador elec zocalo 25 kWseccion 270-1161ros 10 kW fd = 100%10000110000resto fd = 75%150000.7511250AA 3 kVA00(iv)Cocina Electrica 14 kW1200060002000800(v)Calentador de agua 3 kW300013000calentador de tina caliente400014000(vi)cargas adicionalessecadora de ropa40000.251000TOTAL565000.7530973451425502 PREGUNTAHOSPITALREGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-206(1) (a)carga basica12 000m2 X 20W/m2240000240000(b)Areas de alta intensidad300m2 X 100W/m23000030000(c)Calefaccion5000050000AA no considera 30kwiluminacion especializada2000020000cargas de potencia340000340000TOTAL680000680000630000carga sin calefaccion =630000(2) (b)Con aplicacin de fd si AT>900m252.5(i)Calefaccion500000.7537500AA ( no aplica)0(ii)carga sin calefaccion =630000densidad =630000/12000=52.5w52.5(A)52.5*900*0.8472500.837800(B)52.5*(12000-900)*0.655827500.65378787.5(A) + (B)630000416587.5TOTAL680000454087.53 PREGUNTAREGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-202 (1)carga basica At = 120m2(a) (i)1ros 45m2 sera 1500 w15001500(ii)2dos 45m2 sera 1000 w10001000(iii)fracc. sera 1000 w10001000carga basica total35003500(iv)Cocina Electrica 8 kW80006000(v)Calefaccion 12 kW NO APLICAseccion 270-1161ros 10 kW fd = 100%resto fd = 75%AA 12 kVA12000112000(vi) (A)cargas adicionalesCalentador de agua20000.25500secadora30000.25750hidromasaje7471747TOTAL2924723497carga sin calefaccion o AA11497REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-210 (a)sotano y semisotano, AT= 1300m2T-14estacionamiento 10 w/m213000113000(b)alumbrado ext. 15 pts x 100w150011500Ascensores 8500 w c/u, 2u17000117000electrobombas 2190 W219012190electrobomba desague 1500 W150011500extractor co2 2500 w2500125002 puertas levadizas 375 w c/u7501750central intercom 500 w5001500central alarmas 800 w8001800sub total26740126740TOTAL3974039740carga sin calefaccion o AA11497206946REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-202(3)(a)carga sin AA11497(i)100% 1mer Dpto carga mayor11497111497(ii)65% 2 Dptos carga sgts229940.6514946.1(iii)40% 2 Dptos carga sgts229940.49197.6(iv)30% (18-5) Dptos carga sgts1494610.344838.3Total carga dptos20694680479(b)Calefaccion (no aplica)(c)AA 12 kVA *18 Dptos2160001216000(d)cargas fuera de lo Dptos fd=75%397400.7529805TOTAL462686326284

Hoja21ra. PARCIAL DE INSTALACIONES ELECTRICAS 1 (PRACTICA)TEMA B1 PREGUNTA050-110 (a)a181piso256.96Sotanob152do piso256.9613espesor0.2sotano71.828TOTAL585.7495.76REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-110 (a)Area total = 585.74 m2050-200(a) (i)carga basica(ii)1ros 90m2 sera 2500 w25002500sgtes 90m2 o fracc. sera 1000 w5.508222222260006000(iii)Calefaccion 15 KWseccion 270-1161ros 10 kW fd = 100%10000110000resto fd = 75%50000.753750AA (NO APLICA)(iv)Cocina Electrica 14 kW12000600020000.4800(v)Calentador de agua 3 kW300013000calentador de tina caliente400014000(vi)cargas adicionalessecadora de ropa40000.251000TOTAL48500370502 PREGUNTAcolegioREGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-206carga basica At=4800m213(1) (a)Aulas 3500m2 X 50W/m2175000175000(b)area restante 1300m2 X 10W/m21300013000(c)Calefaccion 25 kw (no aplica)AA 35 kw3500035000iluminacion especializada1000010000duchas3500035000cargas de potencia1900019000TOTAL287000287000252000(2) (b)Con aplicacin de fd si AT>900m252.5(i)Calefaccion ( no aplica)AA35000135000(ii)carga sin calefaccion =252000densidad =252000/4800= 52.5w52.5(A)52.5*900*0.75472500.7535437.5(B)52.5*(4800-900)*0.52047500.5102375(A) + (B)252000137812.5TOTAL287000172812.53 PREGUNTAREGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-202 (1)carga basica At = 100m2(a) (i)1ros 45m2 sera 1500 w A=45m215001500(ii)2dos 45m2 sera 1000 w A=45m210001000(iii)fracc. sera 1000 w A= 10m210001000carga basica total35003500(iv)Cocina Electrica 8 kW80006000(v)Calefaccion 14 kWseccion 270-1161ros 10 kW fd = 100%10000110000resto fd = 75%40000.753000AA 2 kVA ( NO APLICA)(vi) (A)cargas adicionalesCalentador de agua20000.25500secadora30000.25750hidromasaje7471747TOTAL3124724497carga sin calefaccion o AA11497calef13000REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-210 (a)sotano y semisotano, AT= 500T-14estacionamiento 10 w/m210000110000(b)alumbrado ext. 15 pts x 100w150011500Ascensores 6500 w650016500electrobombas 2190 W219012190electrobomba desague 1500 W150011500extractor co2 2500 w2500125002 puertas levadizas 375 w c/u7501750central intercom 500 w5001500central alarmas 500 w5001500sub total15940115940TOTAL2594025940carga sin calefaccion o AA11497calef13000229940REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-202(3)(a)carga sin calefaccion11497(i)100% 1mer Dpto carga mayor11497111497(ii)65% 2 Dptos carga sgts229940.6514946.1(iii)40% 2 Dptos carga sgts229940.49197.6(iv)30% (20-5) Dptos carga sgts1724550.351736.5Total dptos22994087377.2(b)Calefaccion 14 Kw * 20 Dptos2801ros 10 kW fd = 100%10000110000(c)resto fd = 75%2700000.75202500(d)cargas fuera de lo Dptos fd=75%259400.7519455TOTAL305940231955535880319332.2

Hoja31ra. PARCIAL DE INSTALACIONES ELECTRICAS 1 (PRACTICA)TEMA C1 PREGUNTA050-110 (a)a191piso197.16Sotanob112do piso197.1612espesor0.2sotano83.5210TOTAL477.84111.365.3093333333REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-110 (a)Area total =477.84 m2050-200(a) (i)carga basica(ii)1ros 90m2 sera 2500 w25002500sgtes 90m2 o fracc. sera 1000 w4.309333333350005000(iii)Calefaccionotro calentador 25 kWseccion 270-1161ros 10 kW fd = 100%10000110000resto fd = 75%150000.7511250AA 3 kVA(iv)Cocina Electrica 14 kW12000600020000.4800(v)Calentador de agua 3 kW300013000calentador de tina caliente400014000(vi)cargas adicionalessecadora de ropa40000.251000TOTAL57500435502 PREGUNTAHOTELREGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-206(1) (a)carga basica2 000m2 X 20W/m24000040000(b)iluminacion especializada2000020000(c)Calefaccion5000050000AA no consideracargas de potencia4000040000TOTAL150000150000100000carga sin calefaccion =100000(2) (b)Con aplicacin de fd si AT>900m250(i)Calefaccion ( no aplica)AA45000145000(ii)carga sin calefaccion =100000densidad =10000/2000= 50w5037.5(A)50*900*0.8450000.836000(B)50*(2000-900)*0.65550000.6535750(A) + (B)10000071750TOTAL145000116750AREASDM (w)3 PREGUNTADEPARTAMENTO A753000DEPARTAMENTO B1005000DEPARTAMENTO C1608000REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-210 (a)sotano AT= 200 m2T-14estacionamiento 10 w/m2200012000(b)alumbrado y tomac250012500TOTAL45004500REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-210 (a)restaurant AT= 250 m2T-1430 w/m275007500alumbrado especial15000115000TOTAL2250022500REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-202(3)(a)(i)100% 1mer Dpto carga mayor800018000(ii)65% 2 Dptos carga sgts160000.6510400(iii)40% 2 Dptos carga sgts130000.45200(iv)30% (18-5) Dptos carga sgts590000.317700(v)25% (4) Dptos carga sgts120000.253000Total dptos10800044300(d)cargas fuera de lo Dptos fd=75%45000.753375restaurants (2)45000145000TOTAL4950048375TOTAL1575000.588412698492675

Hoja41ra. PARCIAL DE INSTALACIONES ELECTRICAS 1 (PRACTICA)TEMA D1 PREGUNTA050-110 (a)a191piso197.16Sotanob112do piso197.1612espesor0.2sotano83.5210TOTAL477.84111.36REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-110 (a)Area total = 477.74 m2050-200(a) (i)carga basica(ii)1ros 90m2 sera 2500 w25002500sgtes 90m2 o fracc. sera 1000 w4.308666666750005000387.844.3093333333(iii)Calefaccion de zocalo 25kwseccion 270-1161ros 10 kW fd = 100%10000110000resto fd = 75%150000.7511250AA 3 kVA(iv)Cocina Electrica 12 kW120006000(v)Calentador de agua 3 kW300013000calentador de tina caliente400014000(vi)cargas adicionalessecadora de ropa40000.251000TOTAL55500427502 PREGUNTACAPACIDAD PARA ACOMETIDA DE TEATRO Y ESTACIONAMIENTOREGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-210 (a)Teatro At = 1000 m2 y sot 500m2T-14densidad =30 w/m2300000.7522500sot estacionamiento 10 w/m2500m2 X 10W/m2500015000(b)iluminacion especializada20000120000(c)Calefaccion 50 KW (NO APLICA)AA 40 KW40000140000cargas de potencia30000130000TOTAL125000117500CAPACIDAD PARA ALIMENTADOR DEL TEATROREGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-210 (a)Teatro At = 1000 m2 y sot 500m2T-14densidad =30 w/m2300000.9528500(b)iluminacion especializada20000120000(c)Calefaccion 50 KW (NO APLICA)AA 40 KW40000140000cargas de potencia30000130000TOTAL120000118500CAPACIDAD PARA ALIMENTADOR DEL ESTACIONAMIENTOREGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-210 (a)sot estacionamiento 10 w/m2T-14500m2 X 10W/m2500015000AREASDM (w)3 PREGUNTADEPARTAMENTO A1105000DEPARTAMENTO B1808000REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-210 (a)sotano AT= 200 m2T-14estacionamiento 10 w/m2200012000(b)alumbrado y tomac200012000TOTAL40004000REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-210 (a)oficina AT= 180 m2T-1450 w/m2900019000TOTAL90009000REGLASDESCRIPCIONPI (Kw)FdDM (Kw)050-202(3)(a)(i)100% 1mer Dpto carga mayor800018000(ii)65% 2 Dptos carga sgts160000.6510400(iii)40% 2 Dptos carga sgts160000.46400(iv)30% (10) Dptos carga sgts500000.315000Total dptos9000039800(d)cargas fuera de lo Dptos fd=75%40000.753000oficinas (2)18000118000TOTAL220000.954545454521000TOTAL1120000.542857142960800